Configure Alarms - 1756-IF6CIS, -IF6I
To configure the alarms on the 1756-IF6I and 1756-IF6CIS:
- Select the channel button for the channel that you want to configure.
- Enter the desired process alarm values for:
- High High
- High
- Low
- Low Low
- Select theUnlatch Allbutton if you want to unlatchallalarms for the channel.
- Select theUnlatchbutton if you want to unlatch the adjacent alarm condition.
- Use the slider bar to visualize where the process alarm trigger parts are set for your process.
- Select theDisable All Alarmsbox if you want to disable alarms for the channel.
- Select theLatch Process Alarmsbox if you want to maintain an alarm-triggered condition for any of the process alarms after the condition ceases.
- Select theLatch Rate Alarmbox to maintain the alarm after the condition ceases.
- Enter a value for which the alarm will not disable, if the input value remains within the range of the alarm trigger point, in theDeadbandbox.
- Enter a value (in Engineering Units per second), for the alarm to trigger when the rate of change between the input samples exceeds the setpoint, in theRate Alarmbox.
- Select:
- OK to accept your edits and close the dialog.
- Cancel to delete your edits and close the dialog.
- Apply to make your edits effective and continue editing.
- Help for assistance with this tab.