Start 1756 analog I/O module calibration
Calibrate module inputs and outputs to obtain optimum accuracy. The
Logix Designer
application calibration screens guide you through the entire process. Before you begin:
- Verify the controller is online and in Program mode.
- Stop the process your output module is controlling or your input module is tracking. Control may be impaired during the calibration process.
- Disconnect input signals and connect test signals. Any control that depends on the normal input signals will not have them during the calibration process.
- Disconnect output signals and connect a suitable measuring instrument. Any control that depends on the outputs from this module will not have them during the calibration process.
- 1756-OF4, -OF8, -IT6I, -IT6I2, -IF6I and -IF6CIS modules can be calibrated in multiple input ranges. Select the appropriateOutput RangeorInput Rangeon theConfigurationtab on theModule Propertiesdialog.IMPORTANT:Note about calibration:
- Entering calibration causes all input channels to freeze at their current values and fault. Control may be impaired.
- Calibration interacts directly with the module overruling any controller that may be trying to use the module.
- Control may be impaired by the calibration process.
- When you begin the calibration process, if a real-time connection is currently open, all module points fault.
To start 1756 analog I/O module calibration
- In theController Organizer, right-click the module and selectProperties.
- In theModule Propertiesdialog, select theCalibrationtab.
- SelectStart Calibration.
Provide Feedback