Calibration Results Low, 1756 Analog Input Modules
From this tab, you can view the results of the measurement of the low reference signal.
If the status column displays | Then |
OK | Select the Next button to continue on to the High Reference test. |
Error | Recheck the wiring to the input channel and the supplied source to ensure the correct signal is being applied. When it is confirmed that the signal is correctly being applied and it is what the channel is currently expecting, select the Retry button to perform low reference again. The calibration process does not succeed until all calibrated channels are OK. To exit a calibration state where the channel will not calibrate, select the Stop button to cancel calibration. |