Module Faults: 16#0800 - 16#08ff

TUV
Code
String
Explanation and Possible Causes/Solutions
16#0800
Network link in path to module is offline.
No interpretation available.
16#0801
Incompatible multi-cast RPI.
No interpretation available.
16#0810
No target application data available.
The controlling application has not initialized the data to be produced by the target device. This may be caused when "Send Data" connections are configured in a target device and the controlling application for that target device has not initialized the data to be produced.
For the target device associated with the "Send Data" connection reporting this connection error, start the controlling application and perform at least one write of data. Refer to the documentation for the target device and its controlling application for information on how to do this.
16#0814
Connection Request Error: Data Type Mismatch.
Invalid connection status information was found.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.