Real Time Sample too small

The work that the module does to:
module
A device, typically an I/O device, that communicates with the controller. The controller, a particular 1756-IB16I or a PanelView are all considered modules.
  • sample the inputs
  • linearize to temperature
  • convert to floating point
  • perform scaling
  • check the various alarms
requires a higher RTS period.
If you are configuring:
Enter an RTS value that is:
a non-isolated 1756-IF8, 1756-IF16 analog input module in float data - high speed mode
8 ms or higher
a 1756-IR6I or 1756 IT6I analog input module in floating point mode
and
a Sensor is specified
50 ms or higher
a module in integer mode
10 ms or higher
a module in floating point mode
25 ms or higher
The RTS indicates how often the modules’ inputs are to be sampled.
There is only one RTS for the entire module.