Channel 2 Current Range Invalid
The current range value for the channel is not a valid value. The following are valid values.
- 0-20 mA - Milliamps x 1000 (0 to 22000)
- 0-20 mA - Signed 2's Complement % (0 to 11000)
- 0-20 mA - Binary (0 to 65535)
- 4-20 mA - Milliamps x 1000 (2000 to 22000)
- 4-20 mA - Signed 2's Complement % (-1250 to +11250)
- 4-20 mA - Signed 2's Complement (-7710 to 32767)
- 4-20 mA - Binary (0 to 65535)
Enter a valid value and apply the changes.