One of the chosen input ranges causes the module to produce data at a slower rate than 5 ms
One of the input ranges you have configured produces data more slowly than the Real Time Sample (RTS) value you configured. Choose a slower RTS or zero to cause the module to use the fastest rate it can make. The input ranges (and corresponding data formats) to which this applies are:
Input Range | Data Format |
4 to 20mA | Signed Two’s Complement |
0 to 20mA | Signed Two’s Complement % |
4 to 20mA | Signed Two’s Complement % |
4 to 20mA | Binary |
4 to 20mA | Offset Binary |
Change the RTS value to a valid value other than 5 (e.g., 0, 10, 15, 20).