Configure a non-isolated analog input module 1756-IF8 and -IF16, floating point
Create a channel-level configuration specific to your application.
To configure a non-isolated analog input module (floating point):
- In the
- In theController Organizer, right-click the module and selectProperties.
- In theModule Properties dialog, select theConfigurationtab.
- Select theChannelbutton to select the channel to configure.
Scalingarea, enter the appropriate scaling values for:- Low Signal
- Low Engineering
- High Signal
- High Engineering
- In theRTSbox, select or type the real time sample period in milliseconds to indicate how often the module scans its input channels.
- In theInput Rangebox, select the desired input operating range.
- In theSensor Offsetbox, select the appropriate offset value for the calibration bias.
- In theDigital Filterbox, select or type the desired filter time constant, in milliseconds.
- In theModule Filter (-3 dB)box, select the filter frequency for the entire module. The filter attenuates the input signal beginning at the specified frequency.
- SelectApplyto save the changes and continue editing, or selectOKto save the changes and close the dialog.