Module Data Types 1794-IC16
The table below lists and describes the module-defined data types for the 1794-IC16 Digital Input module. It includes information for input (as indicated by an "I") and configuration (as indicated by a "C").
Tip: | FLEX I/O is based on 16-bit INTs and not 32-bit DINTs. Using 16-bit INTs in instructions that are optimized for 32-bit DINTs may decrease performance with certain instructions. |
Module-defined Data Type: AB: 1794_DI_16:I:0
This module-defined data type does not apply to modules having Rack Optimization selected for the Comm Format and does not appear among the Module Tags in the RSLogix software.
Member Name | Type | Default Display Style | Description |
Fault | DINT | Binary | Fault - Used for Input Data Validation 0 = Valid Data 1 = Invalid Data - if the connection to the module has been lost, or if the module has a severe hardware fault, the lower 8 bits are set to 1. |
Data | INT | Binary | Input Data - Input data for the module. |
Module-defined Data Type: AB:1794_DI_Filter16:C:0
Member Name | Type | Default Display Style | Description |
Config | INT | Binary | Configuration data. |
FiIter_0 | BOOL | Decimal | Indicates the delay time for the module. |
Filter_1 | BOOL | Decimal | Indicates the delay time for the module. |
FiIter_2 | BOOL | Decimal | Indicates the delay time for the module. |
FiIter_3 | BOOL | Decimal | Indicates the delay time for the module. |
FiIter_4 | BOOL | Decimal | Indicates the delay time for the module. |
FiIter_5 | BOOL | Decimal | Indicates the delay time for the module. |
The Input Filter Time values for this module are shown below.
(Points 11-0) Filter_0, _1, _2 | (Points 15-12) Filter_3, _4, _5 | Maximum Value | ||||
2 | 1 | 0 | 5 | 4 | 3 | |
0 | 0 | 0 | 0 | 0 | 0 | 0.25 |
1 | 0 | 0 | 1 | 0 | 0 | 0.50 |
0 | 1 | 0 | 0 | 1 | 0 | 1 |
1 | 1 | 0 | 1 | 1 | 0 | 2 |
0 | 0 | 1 | 0 | 0 | 1 | 4 |
1 | 0 | 1 | 1 | 0 | 1 | 8 |
0 | 1 | 1 | 0 | 1 | 1 | 16 |
1 | 1 | 1 | 1 | 1 | 1 | 32 |