Invalid Safe State Configuration
You have entered an invalid safe state configuration.
Select a proper safe state value from the list below and continue configuring the module.
Important: | To use the Safe State feature, you must set the Communication Fault Behavior or the Program Mode Behavior to Apply Safe State to Outputs . |
Output Configuration Page
Voltage/Current Range Field | Safe State Value (Decimal) |
None | 0 |
4 to 20 mA – Signed Two’s Complement | -32768 – 32767 |
-10 to 10 V – Signed Two’s Complement | -32768 – 32767 |
-5 to 5 V – Signed Two’s Complement | -32768 – 32767 |
0 to 20 mA – Signed Two's Complement % | 0 – 10500 |
4 to 20 mA – Signed Two's Complement % | -2500 – 10500 |
0 to 10V – Signed Two's Complement % | 0 – 10500 |
-10 to 10V – Signed Two's Complement % | -10500 – 10500 |
-20 to 20 mA – Offset Binary | 32768 – 65535 |
All others | 0 – 65535 |