Configure Input Channels 1794-IF2XOF2
To configure the input channels for the 1794-IF2XOF2I FLEX I/O analog Combo module:
- Position the cursor on the module you want to configure, and right-click the mouse button and select Properties.
- Click the Input Configuration tab.
- Select a Voltage/Current Range and Data Format for each channel from the Voltage/Current Range listbox.
- Select a Conversion Rate for each channel from the Conversion Rate listbox.
- Select a Low Pass Time Constant option from the Low Pass Time Constant listbox.
- Choose the desired Real Time Sample value from the Real Time Sample listbox.
- Do not check the Interleave Module Interrupts check box unless you know you have use for this option.The Interleave Module Interrupts feature is useful only in limited circumstances and can only be enabled when you configured a module’s Conversion Rate to 1200 Hz, Low Pass Time Constant to None, and Real Time Sampling period to 0 for ALL channels on the module.
- Click:
- OK to accept your edits and close the dialog.
- Cancel to delete your edits and close the dialog.
- Apply to make your edits effective and continue editing.
- Help for assistance with this tab.