Module Faults: 16#0200 - 16#02ff
These are the module faults: 16#0200 - 16#02ff.
Code | String | Explanation and Possible Causes/Solutions |
---|---|---|
16#0203 | Connection timed out. | The owner or originator recognizes that the target device is on the network or backplane, however, I/O data and messages are not being responded to. In other words, the target can be reached, but its response is not as expected. For example, this fault may be indicated where multicast Ethernet packets are not returned. When this fault occurs, the controller usually attempts to continuously remove and remake the connection. If you are using FLEX I/O modules, verify that you are using the correct terminal device. |
16#0204 | Connection Request Error: Connection request timed out. | The controller is attempting to make a connection, however, the target module is not responding. The device also appears to be missing from the backplane or network. To recover, take these actions:
If you are using FLEX I/O modules, verify that the correct terminal block is in use. |
16#0205 | Connection Request Error: Invalid parameter. | Either:
|
16#0206 | Connection Request Error: Requested size too large. | Either:
|