Voltage/Current Range Valid Combinations 1794-IF2XOF2I
These are the valid combinations that you can use to configure the voltage and current range for each channel of your module. The corresponding data format appears to the right of the range.
Voltage/Current Range | Data Format |
None | 0 |
0 to 20mA | Signed Two’s Complement % |
0 to 20mA | Binary |
-20 to 20mA | Offset Binary |
0 to 10V | Signed Two’s Complement % |
0 to 10V | Binary |
0 to 5V | Binary |
-10 to 10V | Signed Two’s Complement |
-10 to 10V | Signed Two’s Complement % |
-10 to 10V | Offset Binary |
-5 to 5V | Signed Two’s Complement |
-5 to 5V | Offset Binary |
4 to 20mA | Signed Two’s Complement |
4 to 20mA | Signed Two’s Complement % |
4 to 20mA | Binary |
4 to 20mA | Offset Binary |