Service Codes for Axis Configuration - 1756-PLS
The table contains information that must be entered on the
Message Configuration
dialog Configuration
tab to perform the 1756-PLS module services.Enter the following: | To send an Axis Configuration Message: | To send a Limit Switch Configuration Message: | To send a 1756-PLS Offsets Message: | To send a 1756-PLS Input Registration Message: | |
Service Code | 16# 4c | 16# 4c | 16# 4b | 16# 4b | |
Object Type | 4 | 4 | 4 | 4 | |
Object ID | 17 | 33 | 37 | 36 | |
Source | Local:[n]:C (AB:1756_PLS_Axis:C:0) | Local:[n]:I | N/A | N/A | |
Number of Elements | 44 | 124 | 0 | 0 | |
Destination | N/A | N/A | PlsOffsetsData (AB_1756_PLS_Offsets_I) | PlsInputRegistration (AB_1756_PLS_Registration_I) |