Calibration Results High, 1756 Analog Input Modules

This tab displays the results of the high reference measurement of the calibration process.
If the status column displays:
Then:
OK
Select the
Next
button to continue.
Error
Recheck the wiring to the input channel and the supplied source to ensure the correct signal is being applied. When it is confirmed that the signal is correctly being applied and it is what the channel is currently expecting, select the
Retry
button to perform low reference again. The calibration process does not succeed until all calibrated channels are OK. To exit a calibration state where the channel will not calibrate, select the
Stop
button to cancel calibration.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.