Configure the 1756-IF6I and -IF6CIS in Floating Point Mode
Use this procedure to configure the 1756-IF6I and 1756-IF6CIS in floating point mode.
- Select the channel button for the desired channel to configure.
- Enter the appropriate scaling values for:
- Low Signal
- Low Engineering
- High Signal
- High Engineering
- Select the down arrow to select the desired input operating range
- Enter the appropriate offset value for the calibration bias.
- Select the down arrow in theNotch Filterbox to select the desired filter frequency
- Select the up and down arrows in theDigital Filterbox to select the desired filter time constant in milliseconds.
- Select the up and down arrows in theRTSbox to enter the Real Time Sample period in milliseconds.
- SelectOKto save the changes and close the dialog.