Calibration Results High, 1756 Analog Output Modules
Use this tab to view the results of the calibration process.
If the status column displays: | Then: |
OK | Select the Next button to continue on to the High Reference test. |
Error | Recheck the wiring to the output channel, verify the correct signal is being measured, and double-check that the values you entered are valid. After confirming the signal measurement on the channel, select the Retry button to retry the calibration. Continued calibration errors may indicate a channel failure. To exit a calibration state where the channel will not calibrate, select the Stop button to cancel calibration. The calibration process does not succeed until all calibrated channels are OK. |