PPID shed settings
Use the
Sheds
tab on the PPID Properties
dialog box to configure shed settings for Process Proportional + Integral + Derivative (PPID) instructions.To configure shed settings for PPID instructions
- On the instruction in the routine, perform one of these actions:
- On the Ladder or FBD instruction, select .
- In the Structured Text editor, right-click the tag name and selectConfigure <tag name>.
- UnderAdvanced, select theShedstab.
- Select the shed settings for a CV fail:
- Latch shed action until reset. Select to latch the CV, SP, and loop mode shed actions triggered by CV fail.
- CV action. Select the shed action for the CV when the CV fails:Hold last CVorUse shed CV.
- SP action. Select the shed action for the SP when the CV fails:No action,Hold last SP,Use shed SP, orUse last PV.
- Loop mode action. Select the shed action for the loop mode when CV fails:No action,Manual, orAuto/Manual.
- Select the shed settings for a PV fail:
- Latch shed action until reset. Select to latch the CV, SP, and loop mode shed actions triggered by PV fail.
- CV action. Select the shed action for the CV when the PV fails:Hold last CVorUse shed CV.
- SP action. Select the shed action for the SP when the PV fails:No action,Hold last SP,Use shed SP.
- Loop mode action. Select the shed action for the loop mode when PV fails:No action,Manual, orAuto/Manual.
- Select the shed settings for an SP fail:
- Latch shed action until reset. Select to latch the CV, SP, and loop mode shed actions triggered by SP fail.
- CV action. Select the shed action for the CV when the SP fails:No action,Hold last CV,Use shed CV.
- SP action. Select the shed action for the SP when the SP fails:Hold last SP,Use shed SP, orUse last PV.
- Loop mode action. Select the shed action for the loop mode when SP fails:No action,Manual, orAuto/Manual.
- Select the shed settings for Interlock not OK:
- Latch shed action until reset. Select to latch the CV, SP, and loop mode shed actions triggered by Interlock not OK.
- CV action. Select the shed action for the CV on Interlock not OK:No action,Hold last CV, orUse shed CV.
- SP action. Select the shed action for the SP on Interlock not OK:No action,Hold last SP,Use shed SP, orUse last PV.
- Loop mode action. Select the shed action for the loop mode on Interlock trip:No action,Manual, orAuto/Manual.
- Select the shed values for CV and SP:
- Shed value for CV: Enter or monitor the value to be used for the CV when shed CV is selected as CV action.
- Shed value for SP: Enter or monitor the value to be used for the SP when shed SP is selected as SP action.
- When online with the controller, monitor theDevice state,Device issues, andDevice modeindicators at the bottom left of the dialog box:
- Device state. When theLogix Designerapplication is online with the controller, displays the current device state, suchSP rampingorCV held.
- Device issues. When theLogix Designerapplication is online with the controller, displays fault conditions, such asPV uncertain,SP fail, orConfiguration error.
- Device mode. When theLogix Designerapplication is online with the controller, displays the current device mode:
- Manual
- Auto
- Cascade (no Ratio)
- Ratio
- SelectApply.