PD4SD time settings
Use the
Advanced > Time configuration
tab on the PD4SD Properties
dialog box to configure time parameters for Process Discrete 2-, 3-, or 4-State Device (PD4SD) instructions.To configure time settings for PD4SD instructions
- On the instruction in the routine, perform one of these actions:
- On the Ladder or FBD instruction, select .
- In the Structured Text editor, right-click the tag name and selectConfigure <tag name>.
- Select theAdvanced > Time configurationtab.
- Configure these settings:
- Time to pulse output. Enter the number of seconds to pulse each output. Enter0to hold the output continuously.
- Feedback delay for loopback test or when feedback not used.Enter the number of seconds to delay feedback for a loopback test or when the feedback is not used. Use this setting to configure a virtual feedback time.
- Time after new state requested to reach that state before fault. Enter the number of seconds to allow for device state feedback after a state command. If state feedback is not received within the allotted time, the instruction reports aPosition Failurestatus.
- Time to sound audible on commanded energize. Enter the number of seconds to sound an audible notification when the device is commanded to energize.
- SelectApply.
Provide Feedback