Enhanced Select (ESEL)

This information applies to the
CompactLogix
5370,
ControlLogix
5570,
Compact GuardLogix
5370,
GuardLogix
5570,
Compact GuardLogix
5380,
CompactLogix
5380,
CompactLogix
5480,
ControlLogix
5580, and
GuardLogix
5580 controllers.
The Enhanced Select (ESEL) instruction lets you select one of as many as six inputs. Selection options include:
  • Manual select (by operator or by program)
  • High select
  • Low select
  • Median select
  • Average (mean) select
Available Languages
Ladder Diagram
This instruction is not available in ladder diagram logic.
Function Block
ESEL_FBD_avail_v31
Structured Text
ESEL(ESEL_tag);
Operands
Function Block
Operand
Type
Format
Description
ESEL tag
SELECT_ENHANCED
Structure
ESEL structure
SELECT_ENHANCED Structure
Input Parameter
Data Type
Description
EnableIn
BOOL
Enable input. If false, the instruction does not execute and outputs are not updated.
Default is true.
In1
REAL
The first analog signal input to the instruction.
Valid = any float
Default = 0.0
In2
REAL
The second analog signal input to the instruction.
Valid = any float
Default = 0.0
In3
REAL
The third analog signal input to the instruction.
Valid = any float
Default = 0.0
In4
REAL
The fourth analog signal input to the instruction.
Valid = any float
Default = 0.0
In5
REAL
The fifth analog signal input to the instruction.
Valid = any float
Default = 0.0
In6
REAL
The sixth analog signal input to the instruction.
Valid = any float
Default = 0.0
In1Fault
BOOL
Bad health indicator for In1. If In1 is read from an analog input, then In1Fault is normally controlled by the fault status on the analog input. If all the InnFault inputs are true, the instruction sets the appropriate bit in Status, the control algorithm is not executed, and Out is not updated.
Default = false
In2Fault
BOOL
Bad health indicator for In2. If In2 is read from an analog input, then In2Fault is normally controlled by the fault status on the analog input. If all the InnFault inputs are true, the instruction sets the appropriate bit in Status, the control algorithm is not executed, and Out is not updated.
Default = false
In3Fault
BOOL
Bad health indicator for In3. If In3 is read from an analog input, then In3Fault is normally controlled by the fault status on the analog input. If all the InnFault inputs are true, the instruction sets the appropriate bit in Status, the control algorithm is not executed, and Out is not updated.
Default = false
In4Fault
BOOL
Bad health indicator for In4. If In4 is read from an analog input, then In4Fault is normally controlled by the fault status on the analog input. If all the InnFault inputs are true, the instruction sets the appropriate bit in Status, the control algorithm is not executed, and Out is not updated.
Default = false
In5Fault
BOOL
Bad health indicator for In5. If In5 is read from an analog input, then In5Fault is normally controlled by the fault status on the analog input. If all the InnFault inputs are true, the instruction sets the appropriate bit in Status, the control algorithm is not executed, and Out is not updated.
Default = false
In6Fault
BOOL
Bad health indicator for In6. If In6 is read from an analog input, then In6Fault is normally controlled by the fault status on the analog input. If all the InnFault inputs are true, the instruction sets the appropriate bit in Status, the control algorithm is not executed, and Out is not updated.
Default = false
InsUsed
DINT
Number of inputs used. This defines the number of inputs the instruction uses. The instruction considers only In1 through In
InsUsed
in high select, low select, median select, and average select modes. If this value is invalid, the instruction sets the appropriate bit in status. The instruction does not update Out if InsUsed is invalid and if the instruction is not in manual select mode and if Override is cleared.
Valid =1 to 6
Default = 1
Selector Mode
DINT
Selector mode input. This value determines the action of the instruction.
0 = manual select
1 = High select
2 = Low select
3 = Median select
4 = Average select
If this value is invalid, the instruction sets the appropriate bit in Status and does not update Out.
Valid = 0 to 4
Default = 0
ProgSelector
DINT
Program selector input. When the selector mode is manual select and the instruction is in Program control, ProgSelector determines which input (In1-In6) to move into Out. If ProgSelector = 0, the instruction does not update Out. If ProgSelector is invalid, the instruction sets the appropriate bit in Status. If invalid and the instruction is in Program control, and the selector mode is manual select or Override is set, the instruction does not update. Out.
Valid = 0 to 6
Default = 0
OperSelector
DINT
Operator selector input. When the selector mode is manual select and the instruction is in Operator control, OperSelector determines which input (In1-In6) to move into Out. If OperSelector = 0, the instruction does not update Out. If OperSelector is invalid, the instruction sets the appropriate bit in Status. If invalid and the instruction is in Operator control, and the selector mode is manual select or Override is set, the instruction does not update Out.
Valid = 0 to 6
Default = 0
ProgProgReq
BOOL
Program program request. Set to true by the user program to request Program control. Ignored if ProgOperReq is true. Holding this true and ProgOperReq false locks the instruction into Program control.
Default is false.
ProgOperReq
BOOL
Program operator request. Set to true by the user program to request Operator control. Holding this true locks the instruction into Operator control.
Default is false.
ProgOverrideReq
BOOL
Program override request. Set to true by the user program to request the device to enter Override mode. In Override mode, the instruction will act as a manual select.
Default is false.
OperProgReq
BOOL
Operator program request. Set to true by the operator interface to request Program control. The instruction clears this input to false.
Default is false.
OperOperReq
BOOL
Operator operator request. Set to true by the operator interface to request Operator control. The instruction clears this input to false.
Default is false.
ProgValueReset
BOOL
Reset program control values. When true, all the program request inputs are cleared to false on each execution of the instruction.
Default is false.
Output Parameter
Data Type
Description
EnableOut
BOOL
Indicates if instruction is enabled. Cleared to false if Out overflows.
Out
REAL
The calculated output of the algorithm.
SelectedIn
DINT
Number of input selected. The instruction uses this value to display the number of the input currently being placed into the output. If the selector mode is average select, the instruction sets SelectedIn = 0.
ProgOper
BOOL
Program/Operator control indicator. Set to true when in Program control. Cleared to false when in Operator control.
Override
BOOL
Override mode. Set to true when the instruction is in Override mode.
Status
DINT
Status of the function block.
InstructFault (Status.0)
BOOL
The instruction detected one of the following execution errors. This is not a minor or major controller error. Check the remaining status bits to determine what occurred.
InsFaulted (Status.1)
BOOL
InnFault inputs for all the used Inn inputs are true.
InsUsedInv (Status.2)
BOOL
Invalid InsUsed value.
SelectorModeInv (Status.3)
BOOL
Invalid SelectorMode value.
ProgSelectorInv (Status.4)
BOOL
Invalid ProgSelector value.
OperSelectorInv (Status.5)
BOOL
Invalid OperSelector value.
Structured Text
Operand
Type
Format
Description
ESEL tag
SELECT_ENHANCED
structure
ESEL structure
See Structured Text Syntax for more information on the syntax of expressions within structured text.
Description
The ESEL instruction operates as follows
Condition
Action
SelectorMode = 0 (manual select) or
Override is true, ProgOper is false and OperSelector is not equal to 0
Out = In[OperSelector]
SelectedIn = OperSelector
SelectorMode = 0 (manual select) or
Override is true, ProgOper is true and ProgSelector is not equal to 0
Out = In[ProgSelector]
SelectedIn = ProgSelector
SelectorMode = 1 (high select) and
Override is false
Out = maximum of In[InsUsed]
SelectedIn = index to the maximum input value
SelectorMode = 2 (low select) and
Override is false
Out = minimum of In[InsUsed]
SelectedIn = index to the minimum input value
SelectorMode = 3 (median select) and
Override is false
Out = median of In[InsUsed]
SelectedIn = index to the median input value
SelectorMode = 4 (average select) and
Override is false
Out = average of In[InsUsed]
SelectedIn = 0
For SelectorMode 1 through 4, a bad health indication for any of the inputs causes that bad input to be disregarded in the selection. For example, if SelectorMode = 1 (high select) and if In6 had the highest value but had bad health, then the next highest input with good health is moved into the output.
For high or low select mode, if two inputs are equal and are high or low, the instruction outputs the first found input. For median select mode, the median value always represents a value selected from the available inputs. If more than one value could be the median, the instruction outputs the first found input.
Switch Between Program Control and Operator Control
The following diagram shows how the ESEL instruction changes between Program control and Operator control.
ESEL Switch between program and operator control
(1) You can lock the instruction in Operator control mode by leaving ProgOperReq true.
(2) You can lock the instruction in Program control mode by leaving ProgProgReq true while ProgOperReq is false.
Affects Math Status Flags
No
Major/Minor Faults
None specific to this instruction. See Common Attributes for operand-related faults.
Execution
Function Block
Condition/State
Action Taken
Prescan
EnableIn and EnableOut bits are cleared to false.
Tag.EnableIn is false
EnableIn and EnableOut bits are cleared to false.
Tag.EnableIn is true
EnableIn and EnableOut bits are set to true.
The instruction executes
Instruction first run
The instruction is set to Operator control.
Instruction first scan
N/A
Postscan
EnableIn and EnableOut bits are cleared to false.
Structured Text
Condition/State
Action Taken
Prescan
See Prescan in the Function Block table.
Normal Execution
See Tag.EnableIn is true in the Function Block table.
Postscan
See Postscan in the Function Block table.
Example
This ESEL instruction selects In1, In2, or In3, based on the SelectorMode. In this example, SelectorMode = 1, which means high select. The instruction determines which input value is the greatest and sets Out = greatest In.
Function Block
ESEL_FBD_ex_v31
Structured Text
ESEL_01.In1 := analog_input1;
ESEL_01.In2 := analog_input2;
ESEL_01.In3 := analog_input3;
ESEL_01.SelectorMode := 1;
ESEL(ESEL_01);
selected_value := ESEL_01.Out;
Provide Feedback