Calibration Results Low, 1756 Analog Input Modules

From this tab, you can view the results of the measurement of the low reference signal.
If the status column displays
Then
OK
Select the
Next
button to continue on to the High Reference test.
Error
Recheck the wiring to the input channel and the supplied source to ensure the correct signal is being applied. When it is confirmed that the signal is correctly being applied and it is what the channel is currently expecting, select the
Retry
button to perform low reference again. The calibration process does not succeed until all calibrated channels are OK. To exit a calibration state where the channel will not calibrate, select the
Stop
button to cancel calibration.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.