Calibration Results Low, 1756 Analog Output Modules

Use this tab to view the results of the calibration process.
If the status column displays:
Then:
OK
Select the
Next
button to continue on to the High Reference test.
Error
Recheck the wiring to the output channel, verify the correct signal is being measured, and double-check that the values you entered are valid. After confirming the signal measurement on the channel, select the
Retry
button to retry the calibration. Continued calibration errors may indicate a channel failure. To exit a calibration state where the channel will not calibrate, select the
Stop
button to cancel calibration. The calibration process does not succeed until all calibrated channels are OK.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.