Configure 1756 isolated floating point analog output modules

Create a channel-level configuration specific to your application.
To configure isolated floating point analog output modules:
    1. In the
      Controller Organizer
      , right-click the module and select
      Properties
      .
    2. In the
      Module Propertie
      s dialog, select the
      Configuration
      tab.
    3. Select the
      Channel
      button to select the channel to configure.
    In the
    Scaling
    area, enter the appropriate scaling values for:
    • Low Signal
    • Low Engineering
    • High Signal
    • High Engineering
  1. In the
    Sensor Offset
    box, enter the appropriate offset value for the calibration bias.
  2. Select the
    Hold for Initialization
    check box if you want the module to hold the output signal unchanged until the output value (received from the controller) is within 0.1% of full scale of the value held.
    1. Select
      Apply
      to save the changes and continue editing, or select
      OK
      to save the changes and close the dialog.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.