Configure a non-isolated analog input module 1756-IF8 and 1756-IF16, integer
Create a channel-level configuration specific to your application.
To configure a non-isolated analog input module (integer):
- In the
- In theController Organizer, right-click the module and selectProperties.
- In theModule Properties dialog, select theConfigurationtab.
- Select theChannelbutton to select the channel to configure.
Input Rangebox, select the input operating range for each channel. - In theRTSbox, select or type the real time sample period in milliseconds to indicate how often the module scans its input channels.
- In theModule Filter (-3 dB)box, select the filter frequency for the entire module. The filter attenuates the input signal beginning at the specified frequency.
- SelectApplyto save the changes and continue editing, or selectOKto save the changes and close the dialog.