Configure a non-isolated analog output module- (integer
Create a channel-level configuration specific to your application.
To configure a non-isolated analog output module (integer):
- In theController Organizer, right-click the module and clickProperties.
- On theModule Properties dialog box, click theConfigurationtab.
- Select theChannel button to select the channel to configure.
- In theOutput Rangecolumn, select the output range.
- (optional) Select theHold for Initcheck box to hold the output signal unchanged until the output value that is received from the controller is within 0.1% of full scale of the value held.
- In theFault Statecolumn, select how the output channel reacts if the connection to the owner controller is lost:
- Hold.Output channel remains at the last output value.
- User.Output channel goes to the value specified inUser Fault Value.IMPORTANT:If you selectUser, enter a value in theUser Fault Valuecolumn and select theRamp to Faultcheck box for each output point for which you want to enable ramping when a fault occurs. The value ramps at the ramp rate limit from the current output value to the fault value.
- In theProgram Statecolumn, select how the output channel reacts if the owner controller is switched into Program mode:
- Hold.Output channel remains at the last output value.
- User.Output channel goes to the value specified inUser Program Value.IMPORTANT:If you selectUser, enter a value in theUser Fault Valuecolumn and select theRamp to Faultcheck box for each output point for which you want to enable ramping when a program command is received from the controller. The value ramps at the ramp rate limit from the current output value to the program value.
- In theRate Limit (Cnts/S)column, enter the maximum rate of change in the output signal for each output point in counts per second.
- If communications fail in Program Mode, select how the output channel reacts.
- Leave outputs in Program Mode state
- Change outputs to Fault Mode state
- SelectApplyto save the changes and continue editing, or selectOKto save the changes and close the dialog.