- Studio 5000 Logix Designer
- Tasks, programs, and routines
- Add-On Instructions
- Controller Organizer
- Logical Organizer
- Alarms
- Tag-based alarms
- Tag Editor and Data Monitor
- Configure settings for Tag Editor and Data Monitor
- Equipment phases
- Equipment Sequences
- Equipment Sequence Diagrams
- Ladder Editor
- Structured Text Editor
- Sequential Function Chart Editor
- Define the steps of an SFC process
- PlantPAx instruction properties
- Controller Properties
- Editing Controller Properties
- Controller Security
- Source Protection
- License Source Protection for Routines and Add-On Instructions
- Module Information
- 1756 ControlLogix I/O Modules
- Instruction Set
Configure Alarms 1756-IT6I, -IT6I2, Floating Point Mode
To configure the alarms on the 1756-IT6I and 1756-IT6I2 modules in floating point mode:
- Select the channel button for the channel that you want to configure.
- Enter the desired process alarm values for:
- High High
- High
- Low
- Low Low
- Select theUnlatch All buttonif you want to unlatchallalarms for the channel.
- Select theUnlatchbutton if you want to unlatch the adjacent alarm condition.
- Use the slider bar to visualize where the process alarm trigger parts are set for your process.
- Select theDisable All Alarmsbox if you want to disable alarms for the channel.
- Select theLatch Process Alarmsbox if you want to maintain an alarm-triggered condition for any of the process alarms after the condition ceases.
- Select theLatch Rate Alarmbox to maintain the alarm after the condition ceases.
- Enter a value for which the alarm will not disable, if the input value remains within the range of the alarm trigger point, in theDeadbandbox.
- Enter a value (in Engineering Units per second), for the alarm to trigger when the rate of change between the input samples exceeds the setpoint, in theRate Alarmbox.
- Select:
- OK to accept your edits and close the dialog.
- Cancel to delete your edits and close the dialog.
- Apply to make your edits effective and continue editing.
- Help for assistance with this tab.
Provide Feedback