Module Data Type - 1794-IF4XOF4I/A

The table below lists and describes module-defined data types for the 1794-IF4XOF4I analog input module. It includes information for input (as indicated by an I), output (as indicated by an O), and configuration (as indicated by a C).
Module-defined Data Type: AB:1794_IF4XOF4I:I:0
Member Name
Type
Default Display Style
Description
Fault
DINT
Binary
Fault - Used for Input Data Validation
0 = Valid Data
1 = Invalid Data - if the connection to the module has been lost, or if the module has a severe hardware fault, the lower 8 bits are set to 1.
Ch0InputData
INT
Binary
Input data for channel 0.
Ch1InputData
INT
Binary
Input data for channel 1.
Ch2InputData
INT
Binary
Input data for channel 3.
Ch3InputData
INT
Binary
Input data for channel 4.
CalibrationDone
BIT
Set to 1 after calibration cycle completed.
CalibrationBad
BIT
Set to 1 if channel calibration coefficients cannot be saved or read properly.
NAMURMode
BIT
CalibrationMode
BIT
Set to 1 when configuration mode is selected. The module status indicator flashes when set.
GeneralFault
BIT
FieldPowerOff
BIT
Set to 1 when the 24V field power fails. The module status indicator flashes when set.
PowerUp
BIT
This member is set when the configuration word is all zeros due to reset or a cleared configuration word. The module status indicator flashes when set.
Ch0InputUnderrange
BIT
This member is set when input channel 0 is below a preset limit defined by the selected configuration.
Ch1InputUnderrange
BIT
This member is set when input channel 1 is below a preset limit defined by the selected configuration.
Ch2InputUnderrange
BIT
This member is set when input channel 2 is below a preset limit defined by the selected configuration.
Ch3InputUnderrange
BIT
This member is set when input channel 3 is below a preset limit defined by the selected configuration.
Ch0InputOverrange
BIT
This member is set when input channel 0 is above a preset limit defined by the selected configuration.
Ch1InputOverrange
BIT
This member is set when input channel 1 is above a preset limit defined by the selected configuration.
Ch2InputOverrange
BIT
This member is set when input channel 3 is above a preset limit defined by the selected configuration.
Ch3InputOverrange
BIT
This member is set when input channel 4 is above a preset limit defined by the selected configuration.
Ch0OutputOpenWire
BIT
This member is set when the output channel 0 current loop is open.
Ch1OutputOpenWire
BIT
This member is set when the output channel 1 current loop is open.
Ch2OutputOpenWire
BIT
This member is set when the output channel 2 current loop is open.
Ch3OutputOpenWire
BIT
This member is set when the output channel 3 current loop is open.
Module-defined Data Type: AB:1794_IF4XOF4I:O:0
Member Name
Type
Default
Display Style
Description
OpenWireReset
BIT
Output0:12
SafeStateConfig0
SafeStateConfig1
BIT
Designates the source of the Safe State data when output enable is 0.
safe state
The condition that an output module maintains in the event of a network communication error, or when the controller enters the program mode. When either of these situations occur, the outputs automatically switch to the configured state (for digitals) or to the value (for analogs).
OututEnable
BIT
Always keep this member set to 1. It must be a 1 in order for the Hold For Initialization feature to function.
Ch0OutputData
INT
Output data for channel 0.
Ch1OutputData
INT
Output data for channel 1.
Ch2OutputData
INT
Output data for channel 2.
Ch3OutputData
INT
Output data for channel 3.
Module-defined Data Type: AB:1794_IF4XOF4I:C:0
Member Name
Type
Default
Display Style
Description
Ch0InputRangeType_0
BIT
Include Input channel 0 in range type.
Ch0InputRangeType_1
BIT
Include Input channel 1 in range type.
Ch1InputRangeType_2
BIT
Include Input channel 2 in range type.
Ch1InputRangeType_3
BIT
Include Input channel 3 in range type.
Ch2InputRangeType_4
BIT
Include Input channel 4 in range type.
Ch2InputRangeType_5
BIT
Include Input channel 5 in range type.
Ch3InputRangeType_6
BIT
Include Input channel 6 in range type.
Ch3InputRangeType_7
BIT
Include Input channel 7 in range type.
Ch0OutputRangeType_8
BIT
Include Output channel 8 in range type.
Ch0OutputRangeType_9
BIT
Include Output channel 9 in range type.
Ch1OutputRangeType_10
BIT
Include Output channel 10 in range type.
Ch1OutputRangeType_11
BIT
Include Output channel 11 in range type.
Ch2OutputRangeType_12
BIT
Include Output channel 12 in range type.
Ch2OutputRangeType_13
BIT
Include Output channel 13 in range type.
Ch3OutputRangeType_14
BIT
Include Output channel 14 in range type.
Ch3OutputRangeType_15
BIT
Include Output channel 15 in range type.
Ch0InputRate_0
BIT
Include Input channel 0 in rate.
Ch0InputRate_1
BIT
Include Input channel 1 in rate.
Ch1InputRate_2
BIT
Include Input channel 2 in rate.
Ch1InputRate_3
BIT
Include Input channel 3 in rate.
Ch2InputRate_4
BIT
Include Input channel 4 in rate.
Ch2InputRate_5
BIT
Include Input channel 5 in rate.
Ch3InputRate_6
BIT
Include Input channel 6 in rate.
Ch3InputRate_7
BIT
Include Input channel 7 in rate.
Ch0InputFilter_0
BIT
Include Input channel 0 in filter.
Ch0InputFilter_1
BIT
Include Input channel 1 in filter.
Ch1InputFilter_2
BIT
Include Input channel 2 in filter.
Ch1InputFilter_3
BIT
Include Input channel 3 in filter.
Ch2InputFilter_4
BIT
Include Input channel 4 in filter.
Ch2InputFilter_5
BIT
Include Input channel 5 in filter.
Ch3InputFilter_6
BIT
Include Input channel 6 in filter.
Ch3InputFilter_7
BIT
Include Input channel 7 in filter.
Ch0InputCalibrate
BIT
Include Input channel 0 in calibration.
Ch1InputCalibrate
BIT
Include Input channel 1 in calibration.
Ch2InputCalibrate
BIT
Include Input channel 2 in calibration.
Ch3InputCalibrate
BIT
Include Input channel 3 in calibration.
Ch0IOutputCalibrate
BIT
Include Output channel 0 in calibration.
Ch1OutputCalibrate
BIT
Include Output channel 1 in calibration.
Ch2OutputCalibrate
BIT
Include Output channel 2 in calibration.
Ch3OutputCalibrate
BIT
Include Output channel 3 in calibration.
GainOffsetCalibration
BIT
If set, gain calibration.
gain
The ratio of the magnitude of the output signal with respect to that of the input signal.
In a linear equation (y=mx+b), the parameter (m) is used to drive the dependent variable (y) to a specified value when the independent variable (x) is at a maximum.
If clear, offset calibration.
offset
The steady-state deviation of a controlled variable from a fixed set point. In a linear function (y=mx+b), the parameter (b) is used to drive the dependent variable (y) to zero when the independent variable (x) is zero.
CalibrationClock
BIT
If set to 1, calibration mode starts and coefficients for selected channels are accepted.
If clear, the accepted current calibration coefficients are stored to selected channels, applied and calibration mode is exited.
QuickCalibration
BIT
If set to 1, calibration coefficient is stored to all related configurations for selected channels.
DefaultCalibration
BIT
NAMURCompatible
BIT
SSOpenWireReset
BIT
SSSafeStateConfig0
BIT
Safe state value to use for SafeStateConfig0.
SSSafeStateConfig1
BIT
Safe state value to use for SafeStateConfig1.
SSOutputEnable
BIT
Safe state value to use for OutputEnable.
SSCh0OutputData
INT
Safe State value to use for Ch0OutputData.
SSCh1OutputData
INT
Safe State value to use for Ch1OutputData.
SSCh2OutputData
INT
Safe State value to use for Ch2OutputData.
SSCh3OutputData
INT
Safe State value to use for Ch3OutputData.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.