The table below lists and describes the module-defined data types for the 1794-OE12 module. It includes information for input (as indicated by an "I"), output (as indicated by an "O") and configuration (as indicated by a "C").
Module-defined Data Type: AB:1794_OE12:I:0
Member Name
Type
Default
Display Style
Description
Fault
DINT
Binary
Status
INT
Binary
Ch00OpenWire
Ch01OpenWire
Ch02OpenWire
Ch03OpenWire
Ch04OpenWire
Ch05OpenWire
Ch06OpenWire
Ch07OpenWire
Ch08OpenWire
Ch09OpenWire
Ch10OpenWire
Ch11OpenWire
BIT
Status:0
Status:1
Status:2
Status:3
Status:4
Status:5
Status:6
Status:7
Status:8
Status:9
Status:10
Status:11
BIT
Bit 12 Reserved
GeneralFault
BIT
Status:13
FieldPowerOff
BIT
Status:14
PowerUp
BIT
Status:15
Module-defined Data Type: AB:1794_OE12:O:0
Member Name
Type
Default
Display Style
Description
WireOffReset
BIT
OutputData:12
SafeStateConfig0
BIT
OutputData:13
SafeStateConfig1
BIT
OutputData:14
OutputEnable
BIT
OutputData:15
Ch00Data
Ch01Data
Ch02Data
Ch03Data
Ch04Data
Ch05Data
Ch06Data
Ch07Data
Ch08Data
Ch09Data
Ch10Data
Ch11Data
INT
Module-defined Data Type: AB:1794_OE12:C:0
Member Name
Type
Default
Display Style
Description
Config
INT
Binary
Ch00_01ConfigSelect_0
Ch00_01ConfigSelect_1
Ch02_03ConfigSelect_2
Ch02_03ConfigSelect_3
Ch04_05ConfigSelect_4
Ch04_05ConfigSelect_5
Ch06_07ConfigSelect_6
Ch06_07ConfigSelect_7
Ch08_09ConfigSelect_8
Ch08_09ConfigSelect_9
Ch10_11ConfigSelect_10
Ch10_11ConfigSelect_11
BIT
Config:0
Config:1
Config:2
Config:3
Config:4
Config:5
Config:6
Config:7
Config:8
Config:9
Config:10
Config:11
BIT
Bits 12...15 Reserved
SSSafeStateConfig0
BIT
SSConfig:13
SSSafeStateConfig1
BIT
SSConfig:14
SSOutputEnable
BIT
SSConfig:15
SSCh00OutputData
SSCh01OutputData
SSCh02OutputData
SSCh03OutputData
SSCh04OutputData
SSCh05OutputData
SSCh06OutputData
SSCh07OutputData
SSCh08OutputData
SSCh09OutputData
SSCh10OutputData
INT