Module-defined Data Type: AB:1797_IE8:I:0
Member Name
Type
Default
Display Style
Description
Fault
DINT
Binary
Fault - Used for Input Data Validation
0 = Valid Data
1 = Invalid Data - if the connection to the module has been lost, or if the module has a severe hardware fault, the lower 8 members are set to 1.
Ch0Data
Ch1Data
Ch2Data
Ch3Data
Ch4Data
Ch5Data
Ch6Data
Ch7Data
INT
Decimal
Input data for the selected channel.
Alarms
INT
Binary
Alarms data.
Ch0Underrange
Ch1Underrange
Ch2Underrange
Ch3Underrange
Ch4Underrange
Ch5Underrange
Ch6Underrange
Ch7Underrange
BOOL
Decimal
Underrange-set if the input signal is below the input channel’s minimum range. Ch0 corresponds to channel 0, Ch1 corresponds to channel 1, etc. up to Ch7 corresponding to channel 7.
Ch0Overrange
Ch1Overrange
Ch2Overrange
Ch3Overrange
Ch4Overrange
Ch5Overrange
Ch6Overrange
Ch7Overrange
BOOL
Decimal
Overrange-set if the input signal is above the input channel’s maximum range.
Status1
INT
Binary
Alarms data.
Ch0LocalFault
Ch1LocalFault
Ch2LocalFault
Ch3LocalFault
Ch4LocalFault
Ch5LocalFault
Ch6LocalFault
Ch7LocalFault
BOOL
Decimal
This member is set when the loop to the transmitter or field device is open or shorted.
Ch0RemoteFault
Ch1RemoteFault
Ch2RemoteFault
Ch3RemoteFault
Ch4RemoteFault
Ch5RemoteFault
Ch6RemoteFault
Ch7RemoteFault
BOOL
Decimal
This member is set when the Remote Transmitter Error Up or Down is selected and there is an alarm from the remote transmitter indicating transmitter difficulties, sensor difficulties, or the loop to the sensor is open. If not using a remote transmitter then the bit for the channel indicates a high-high or low-low alarm.
Status2
INT
Binary
Diagnostic data.
Ch0DiagnosticStatus0
Ch1DiagnosticStatus1
Ch2DiagnosticStatus2
Ch3DiagnosticStatus3
BOOL
Decimal
Diagnostic Data: 0=normal, 1=calibration failure, 2=configuration failure (bad Data Format selected), 3=message failure, 4=lead break detection hardware failure, 5=major hardware failure, 6=EEPROM failure, 7=RAM failure, 8=ROM failure, 9=calculation failure, 10-15 are unused.
EDTResponseData
SINT
Decimal
Extended data table response data settings that echo the EDT command data written to the module during calibration.
EDTResponse
SINT
Decimal
Extended data table response settings that echo the EDT command data written to the module during calibration.
ResponseFlag
BOOL
Decimal
Used to determine whether the EDTResponse is enabled.
Module-defined Data Type: AB:1797_IE8:C:0
Member Name
Type
Default
Display Style
Description
Config1
INT
Binary
Configuration information.
FaultEnable_0_3
BOOL
Decimal
Fault Enable for channels 0 through 3.
DataFormat1_0_3
DataFormat2_0_3
DataFormat3_0_3
DataFormat4_0_3
BOOL
Decimal
Data Format for channels 0 through 3.
FilterCutoff5_0_3
FilterCutoff6_0_3
FilterCutoff7_0_3
BOOL
Decimal
Filter Selections for channels 0 through 3.
RemTransmitterError_0_3
BOOL
Decimal
Remote Transmitter Error direction, 0 = Up, 1 = Down for channels 0 through 3.
ErrorLevel9_0_3
ErrorLevel10_0_3
ErrorLevel11_0_3
ErrorLevel12_0_3
ErrorLevel13_0_3
BOOL
Decimal
The resulting value from the calculation: Error Level step increment value * 0.1mA for channels 0 through 3. Valid step values are 0-20.
Config2
INT
Binary
Configuration information.
FaultEnable_4_7
BOOL
Decimal
Fault Enable for channels 4 through 7.
DataFormat1_4_7
DataFormat2_4_7
DataFormat3_4_7
DataFormat4_4_7
BOOL
Decimal
Data Format for channels 4 through 7.
FilterCutoff5_4_7
FilterCutoff6_4_7
FilterCutoff7_4_7
BOOL
Decimal
Filter Selections for channels 4 through 7.
RemTransmitterError_4_7
BOOL
Decimal
Remote Transmitter Error direction, 0 = Up, 1 = Down for channels 4 through 7.
ErrorLevel9_4_7
ErrorLevel10_4_7
ErrorLevel11_4_7
ErrorLevel12_4_7
ErrorLevel13_4_7
BOOL
Decimal
Error Level step value * 0.1mA for channels 4 through 7. Valid values are 0-20.
EDTCommandData
SINT
Decimal
Extended data table response command data settings that echo the EDT command data written to the module during calibration.
EDTCommand
SINT
Decimal
Extended data table command response settings that echo the EDT command data written to the module during calibration.
CommandFlag
BOOL
Decimal
Used to determine whether the EDTCommand is enabled.