Module-defined Data Types (150-SMCDialogPlus)

The tables below list and describe the Input and Output module-defined data types for this module.
Input Data Types
Data Links
Data Type
0
AB:SMCDialogPlus _SP_Drive_8Bytes:I:0
2
AB:SMCDialogPlus _SP_Drive_12Bytes:I:0
4
AB:SMCDialogPlus _SP_Drive_16Bytes:I:0
6
AB:SMCDialogPlus _SP_Drive_20Bytes:I:0
8
AB:SMCDialogPlus _SP_Drive_24Bytes:I:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
DPI Description
LogicStatus
INT
Binary
Logic Status
Enabled
0
BOOL
Decimal
Enabled
Running
1
BOOL
Decimal
Running
Starting
4
BOOL
Decimal
Starting
Stopping
5
BOOL
Decimal
Stopping
Alarm
6
BOOL
Decimal
Alarm
Fault
7
BOOL
Decimal
Fault
AtSpeed
8
BOOL
Decimal
At Speed
Output Data Types
Data Links
Data Type
0
AB: SMCDialogPlus _SP_Drive_4Bytes:O:0
2
AB: SMCDialogPlus _SP_Drive_8Bytes:O:0
4
AB: SMCDialogPlus _SP_Drive_12Bytes:O:0
6
AB: SMCDialogPlus _SP_Drive_16Bytes:O:0
8
AB: SMCDialogPlus _SP_Drive_20Bytes:O:0
Member Name
Bit in
Previous Word
Data Type
Default Display Style
SCANPort Description
LogicCommand
INT
Binary
Logic Command
Stop
0
BOOL
Decimal
Stop
Start
1
BOOL
Decimal
Start
OptionCommand
2
BOOL
Decimal
Option Command
ClearFault
3
BOOL
Decimal
Clear Fault
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.