Real Time Sample too small

Real Time Sample too small

The work that the module does to:
module
A device, typically an I/O device, that communicates with the controller. The controller, a particular 1756-IB16I or a PanelView are all considered modules.
  • sample the inputs
  • linearize to temperature
  • convert to floating point
  • perform scaling
  • check the various alarms
requires a higher RTS period.
If you are configuring:
Enter an RTS value that is:
a non-isolated 1756-IF8, 1756-IF16 analog input module in float data - high speed mode
8 ms or higher
a 1756-IR6I or 1756 IT6I analog input module in floating point mode
and
a Sensor is specified
50 ms or higher
a module in integer mode
10 ms or higher
a module in floating point mode
25 ms or higher
The RTS indicates how often the modules’ inputs are to be sampled.
There is only one RTS for the entire module.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal