Wiring Diagram 1794-IB10XOB6, Input

The recommended Terminal Base for the Input 1794-IB10XOB6 is the 1794-TB3. A wiring diagram to the 1794-TB3 is shown below. The compatible Terminal Base for the 1794-IB10XOB6 is the 1794-TB3S. A wiring diagram for the 1794-TB3S is also shown below.
Typical Simplified Schematic for Input 0
1794IB10XOB6isch
To wire the 1794-IB10XOB6 to a 1794-TB3 or -TB3S Terminal Base Unit, use these steps.
  1. Connect the associated input or output power to the corresponding terminal on the 34-51 row (C) for each as indicated in the table below. (Power terminals 34 thru 51 are internally connected together.)
  2. Connect the +24V dc power to terminal 34 on the 34-51 row (C).
  3. If continuing power to the next terminal base unit, connect a jumper from terminal 51 (+24V dc) on this base unit to terminal 34 on the next base unit.
  4. Connect the associated input or output return to the corresponding terminal on the 16-33 row (B) for each as indicated in the table below. (Returns are internally connected together.)
  5. Connect 24V dc return to terminal 16 on the 16-33 row (B).
  6. If continuing 24V return to the next terminal base unit, connect a jumper from terminal 33 (return) on this base unit to terminal 16 on the next base unit.
  7. Connect the individual input and output wiring to numbered terminals on the 00-15 row (A) as indicated in the table below.
    ATTENTION:
    Total current draw through the terminal base unit is limited to 10A. Separate power connections may be necessary.
Wiring
1794IB10XOB6i