Configure 1797-IBN16 FLEX Ex
Use this feature to filter-out transients in noisy environments. Select a value (in milliseconds) by which to filter the transition from On to Off or from Off to On. The Input Filter Time values in milliseconds begin at 0.25ms and end at 32ms.
To configure the Input Filter Time on the 1797-IBN16 module:
- Select a value (in milliseconds) by clicking the down arrow in the Input Filter Time (ms) – On->Off Off->On list boxes.
- Click the desired Input Mode radio button to choose the method of fault detection and reporting for the selected channels.
- Click:
- OK to accept your edits and close the dialog.
- Cancel to cancel your edits and close the dialog.
- Apply to apply your edits and continue editing.
- Help for Help on this tab.