Advanced tab
Use the
Advanced tab
to view and edit the advanced controller properties.
TIP:
The parameters
System Overhead Time Slice
and During unused System Overhead Time Slice
are not needed by controllers supported by versions 25.00.00 and later of the Logix Designer
application, and have been removed.
TIP:
To open the Advanced tab:
- In theController Organizer, expand theI/O Configurationfolder, and double-click the controller.
- On theController Propertiesdialog box, click theAdvancedtab.
Parameter | Description |
Controller Fault Handler | This program runs when there is a system fault. Valid values include all unscheduled programs. |
Power-Up Handler | This program runs when the processor powers up in Run mode after a power-down in Run mode. Valid values include all unscheduled programs. |
Match Project to Controller | The Logix Designer application verifies that the serial number configured for the project matches the serial number of the controller when going online, downloading, and uploading. Verification does not occur when transferring a project from nonvolatile memory to the controller. Match Project to Controller is only enabled for controllers that support serial numbers. |
Serial Number | The serial number of the controller to which this program is associated. Serial Number is only enabled when Match Project to Controller is selected. |
Allow Consumed Tags to Use RPI Provided by Producer | Connects the consumed tags in the controller to the producer when the producer provides the Requested Packet Interval (RPI). If the RPI of the consumed tag is outside the RPI range of the producer, the connection fails. Allow Consumed Tags to Use RPI Provided by Producer is only enabled when the controller is offline. |
Report Overflow Faults | Reports minor Overflow faults. Report Overflow Faults is only enabled when the controller is offline.The value of this check box is persisted in .ACD, .L5K, and .L5X files and downloaded to the controller. When the value is changed offline, the correlation between the Logix Designer application and the controller is broken. A full download or upload is required to reconnect to the controller.
IMPORTANT:
Selecting Report Overflow Faults may increase application scan time.
NOTE:
Selecting or clearing Report Overflow Faults changes the Safety Instruction Signature ID for Safety Add-On Instructions that include math instructions. |
Enable Automatic Diagnostics | Automatically sends device diagnostic condition updates to applications and client devices supported by FactoryTalk Alarms and Events .
NOTE:
Supported only on CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers. |