Troubleshooting

Troubleshooting

The following sections describe troubleshooting methods for DataView issues that may occur during installation and configuration.
Scenario 1: Error message “404 Not Found” when trying to access the DataView login page.
Login Page
Root Cause:
DataView PostgreSQL or FTAnalyticsDataImporter or FTAnalyticsDataView or FTASecurity service is not running.
DataView application root URL is invalid.
Solution:
Perform the following steps to ensure all the component services are running:
  1. Open the FTADataView log file to verify the error message.
  2. Enter the valid application root URL.
  3. Open the Windows Service management console, verify the following services, DataView PostgreSQL, FTAnalyticsDataImporter, FTAnalyticsDataView, FTASecurity service.
    1. Ensure that the PostgreSQL service is running.
      PostgreSQL Service
    2. Ensure that the FTASecurity service is running.
      FTASecurity Service
    3. Ensure that the FTAnalyticsDataImporter service is running.
      FTAnalyticsDataImporter Service
    4. Ensure that the FTAnalyticsDataView service is running.
      FTAnalyticsDataView Service
Scenario 2: The DataView applications does not load and displays a blank page.
Root Cause:
DataView application lost connectivity with PostgreSQL service.
Solution
: Ensure that the PostgreSQL service is running.
PostgreSQL Service
Scenario 3: Error message “
FT Activation Manage Service is not Active. Please check the connectivity
”.
Root Cause
: DataView lost connectivity with the FTA Activation Service server.
Solution
: Restart the following services:
  1. FactoryTalk Activation Service
  2. FactoryTalk Activation Websocket Service
  3. FTAnalyticsDataView
Scenario 4: Error message “
FTActivation is in Grace Period'. In the log file the error ‘not able to create file FTAMapStore
” displays.
Root Cause
: DataView does not have access to the FTActivation folder and it is not be able to create FTAMapStore file.
Solution
: Perform the following steps:
  1. Ensure that proper permissions are given to the FTActivation folders.
  2. Restart the following services:
    1. FactoryTalk Activation Service
    2. FactoryTalk Activation Websocket Service
    3. FTAnalyticsDataView
Scenario 5: Error message “
The driver not supported
” - when Windows Auth option is used in case of SQL Server.
Root Cause
: The MSSQL driver is not available in JDK.
Solution
: Download the MSSQL driver (version used in the DataView) and place it in JDK bin folder as shown in the following image:
MSSQL Driver
Scenario 6: Error message “
FT Activation Manage Service is not Active. Please check the connectivity
”.
Root Cause
: DataView lost connectivity with the FTA Activation Service server.
Solution
: Perform the following steps:
  1. Stop the services in the following order:
    1. FTAnalyticsDataView
    2. FTAnalyticsDataImporter
    3. PostgreSQL
    4. Elasticsearch
    5. FTASecurity
    6. FactoryTalk Activation Service
    7. FactoryTalk Activation Websocket Service
  2. Start the services in the following order:
    1. FactoryTalk Activation Service
    2. FactoryTalk Activation Websocket Service
    3. PostgreSQL
    4. Elasticsearch
    5. FTASecurity
    6. FTAnalyticsDataImporter
    7. FTAnalyticsDataView
Scenario 7: System encountered an issue while processing request, please contact administrator for further info.
Root Cause
: This issue is encountered for the following reasons:
  1. Incorrect configuration of the following property files
    • dataimporter.property
    • application.property
  2. Activation Service not connected to the DataView server.
  3. Websocket connection issue.
  4. SSL certificate mismatch for DataView and Activation Server.
  5. Websocket port is disabled by firewall need to open the port.
  6. If FTASecurity is in different server and port is disable
Solution
: Perform the following steps:
  1. Stop the services in DataView machine:
    • DataView.service
    • dataImporter.service
    • fta-security.service
  2. Stop the services in FTA Activation Service machine
    • FactoryTalk Activation Helper
    • FactoryTalk Activation Service
    • FactoryTalk Activation WebsocketService
  3. Ensure that the FQDN and the other properties are properly defined in the configuration files. Refer to Table 1 table for file location:
    • application.properties
    • dataimporterproperties.properties
    • WebsocketService.dll.config
  4. Verify that the following properties are correct in the FTASecurity and FTAActivation Websocket configuration files and update as required:
    • certificate file path
    • keystore path
    • truststore path
    • certificate file (<FQDN-hostname>.p12) path and hostname
  5. Open the websocket service port (for example: 27100) in the FTA Activation Service machine.
  6. Enable the FTASecurity service port (for example: 9043) in the FTASecurity machine.
  7. Start the services in FTA Activation Service machine:
    • FactoryTalk Activation Helper
    • FactoryTalk Activation Service
    • FactoryTalk Activation WebsocketService
  8. Start the services in DataView machine:
    • FactoryTalkAnalyticssecurity.service
    • FactoryTalkAnalyticsDataImporter.service
    • FactoryTalkAnalyticsDataView.service
  9. Open the URL,
    https://<FQDN-hostname>/dataview
    in a new web browser to open the DataView application.
    Login Page
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal