Module Data Types - 1794-IJ2, 1794-IJ2I, 1797-IJ2

The table below lists and describes module-defined data types for the 1794-IJ2, 1794-IJ2I, and the 1797-IJ2 modules. It includes information for input (as indicated by an I) and configuration (as indicated by a C) in the module Tag Type name shown on the Controller Tags window in the
Logix Designer
application.
Note that FLEX I/O and Ex is based on 16-bit INTs and not-32-bit DINTs. This may decrease performance with certain instructions.
Module-defined Data Type: AB:1794_IJ2:I:0 (both 1794 and 1797-IJ2 modules use this data type)
Member Name
Type
Default Display Style
Description
Fault
DINT
Binary
Used for Input Data Validation - 0 means the data is valid. If the connection to the module has been lost, or if the module has a severe hardware fault, 1s are represented in this input data type.
Ch0Frequency
INT
Decimal
Calculated value of Frequency for Channel 0. Frequency can be reported down to 1 or 1.0 Hz, depending on the Frequency Range setting. Below a 1 Hz value, 0 is reported. Below a 1.0 Hz value, 0.0 is reported. Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier. If input pulses are not present within the time periods allotted by these parameters, zero frequency (0 or 0.0) is reported, depending additionally on the setting of the Wire Off Fault Detection Mode. When the Frequency exceeds the module’s Max Input Frequency, the Frequency value 32,767 is reported, or- the Frequency value 3,276.7 is reported, depending on the Frequency Range data type.
When the Scaled Frequency exceeds 32,767 or 3,276.7, the Frequency value 32,767 is reported.
If a Wire Off Alarm is detected and enabled, the Frequency reported may be an Unchanged, Maximum (32,767 or 3,276.7 default or the Maximum Frequency value), or Minimum value (1 or 1.0), depending on the selection of the Wire Off Fault Alarm and the Frequency Range data type.
Range: 0...32,767 or 0.0...3,276.7 depending on state of Frequency Range data type, or Freq Range = 0 when the Frequency in Hz. is 0 - 32,767 and
Freq Range = 1 when the Frequency in Hz. is (0.0 - 3,276.7).
Ch0Acceleration
INT
Decimal
Percent of Full Scale or Acceleration for Channel 0. Value of the calculated Frequency scaled by the Maximum Frequency or, calculated value of Acceleration in Hz/s, depending on Frequency or Acceleration Alarm select data type.
Note that percent full scale is calculated accurately up to a maximum of 3,276.7%. Beyond this maximum, the value of 3,276.7% is returned, and a Calculation Failure (9) is set in Diagnostic Status.
Frequency or Acceleration Alarm select data type = 0
Range: 0.0...3,276.7%
Frequency or Acceleration Alarm select data type = 1
Range: -32,768...32,767 Hz/sec (2’s Complement if Negative)
Ch1Frequency
INT
Decimal
Calculated value of Frequency for Channel 1. Frequency can be reported down to 1 or 1.0 Hz, depending on the Frequency Range setting. Below a 1 Hz value, 0 is reported. Below a 1.0 Hz value, 0.0 is reported. Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier. If input pulses are not present within the time periods allotted by these parameters, zero frequency (0 or 0.0) is reported depending additionally on the setting of the Wire Off Fault Detection Mode. When the Frequency exceeds the module’s Max Input Frequency, the Frequency value 32,767 is reported, or- the Frequency value 3,276.7 is reported, depending on the Frequency Range data type.
When the Scaled Frequency exceeds 32,767 or 3,276.7, the Frequency value 32,767 is reported.
If a Wire Off Alarm is detected and enabled, the Frequency reported may be an Unchanged, Maximum (32,767 or 3,276.7 default or the Maximum Frequency value), or Minimum value (1 or 1.0), depending on the selection of the Wire Off Fault Alarm and the Frequency Range data type, or Ch1Frequency Range = 0 when the Frequency in Hz. is 0...32,767 and
Ch1Frequency Range = 1 when the Frequency in Hz. is 0.0...3,276.7.
Ch1Acceleration
INT
Decimal
Percent of Full Scale or Acceleration for Channel 1. Value of the calculated Frequency scaled by the Maximum Frequency or, calculated value of Acceleration in Hz/s, depending on Frequency or Acceleration Alarm select data type.
Note that the percent full scale is calculated accurately up to a maximum of 3,276.7%. Beyond this maximum, the value of 3,276.7% is returned, and a Calculation Failure (9) is set in Diagnostic Status.
Ch1Acceleration = 0
Range: 0.0...3,276.7%
Ch1Acceleration = 1
Range: -32,768...32,767 Hz/sec (2’s Complement if Negative)
Alarms
INT
Binary
Alarm data.
Ch1MissingPulse
BOOL
Decimal
Missing Pulse Alarm (channel 1) – Indicates when no Frequency input pulse has occurred within the period determined by the Minimum Frequency Sampling Time and the Missing Pulse Multiplier. Primary control is given to the Missing Pulse Multiplier to determine when this data type is set. However, if the Missing Pulse Multiplier is set to 0, then the Minimum Frequency Sampling Time characteristics determine when this data type is set.
Ch1WireOff
BOOL
Decimal
Wire Off Fault Alarm (channel 1) – when set, indicates when 24V dc Input (IEC 1+ or Switch Contact with shunt) Wire Off Detection has gone true for any of the Frequency or Gate inputs on a channel that has the Wire Off Fault
Select = 1
Ch1FrequencyAccel
BOOL
Decimal
Frequency or Acceleration Alarm (channel 1) – Changes state from 0 to 1 if the calculated Frequency (actual or scaled) exceeds the user programmed Maximum Frequency, or the absolute value of calculated Acceleration/Deceleration exceeds the user programmed Maximum Acceleration Value.
The Frequency Alarm turns off when the Frequency drops below 95% of the Alarm Value.
The Acceleration Alarm turns off when the Acceleration drops below 90% of the Alarm Value.
Ch1GateState
BOOL
Decimal
Gate Input State (channel 1) – Indicates if there is a valid signal on the gate input. This parameter is only determined once every 0.5 – 2s.
Ch1Direction4
Ch1Direction5
BOOL
Decimal
Direction (channel 1) – Indicates the current Direction of Rotation, using both the Frequency and Gate inputs. (Frequency leads Gate = Clockwise, Gate leads Frequency = CounterClockwise). Used for slow speed detection from 1...1,500 Hz. No or Stopped rotation can be determined by the state of the Missing Pulse Alarm, when it is switched on. A missing Frequency Input generates a Missing Pulse Alarm, a missing Gate Input only generates a No Sensor Present / Detected status (3).
Ch0MissingPulse
BOOL
Decimal
Missing Pulse Alarm (channel 0) – Indicates when no Frequency input pulse has occurred within the period determined by the Minimum Frequency Sampling Time and the Missing Pulse Multiplier. Primary control is given to the Missing Pulse Multiplier to determine when this data type is set. However, if the Missing Pulse Multiplier is set to 0, then the Minimum Frequency Sampling Time characteristics determine when this data type is set.
Ch0WireOff
BOOL
Decimal
Wire Off Fault Alarm (channel 0) – When set, indicates when 24V dc Input (IEC 1+ or Switch Contact with shunt) Wire Off Detection has gone true for any of the Frequency or Gate inputs on a channel that has the Wire Off Fault
Select = 1
Ch0FrequencyAccel
BOOL
Decimal
Frequency or Acceleration Alarm (channel 0) – Changes state from 0 to 1 if the calculated Frequency (actual or scaled) exceeds the user programmed Maximum Frequency, or the absolute value of calculated Acceleration/Deceleration exceeds the user programmed Maximum Acceleration Value.
The Frequency Alarm turns off when the Frequency drops below 95% of the Alarm Value.
The Acceleration Alarm turns off when the Acceleration drops below 90% of the Alarm Value.
Ch0GateState
BOOL
Decimal
Gate Input State (channel 0) – Indicates if there is a valid signal on the gate input. This parameter is only determined once every 0.5 – 2s.
Ch0Direction12
Ch0Direction13
BOOL
Decimal
Direction (channel 0) – Indicates the current Direction of Rotation, using both the Frequency and Gate Inputs.  (Frequency leads Gate = Clockwise, Gate leads Frequency = Counter/Clockwise). Used for slow speed detection from 1...1,5000 Hz. No or Stopped rotation is determined by the state of the Missing Pulse Alarm, when it is switched on. A missing Frequency Input generates a Missing Pulse Alarm. A missing Gate Input generates a No Sensor Present/Detected status (3) only.
DiagnosticStatus
INT
Binary
Diagnostic status data.
DiagnosticStatus0
DiagnosticStatus1 DiagnosticStatus2
DiagnosticStatus3
BOOL
Decimal
Indicate the response from the module, a normal or non-normal operating condition. Follow the table below for settings.
DiagnosticStatus3
DiagnosticStatus2
DiagnosticStatus1
DiagnosticStatus0
Value
0
0
0
0
0=Normal Operation (No Failure)
0
0
0
1
1=Calibration Failure
0
0
1
0
2=Configuration Failure
A minimum Frequency Sample Time value other than 0-9 was selected.
0
0
1
1
3=Message Failure
0
1
0
0
4=Lead Break Detection Hardware Failure
0
1
0
1
5=Major Hardware Failure
0
1
1
0
6=EEPROM Failure
0
1
1
1
7=RAM Failure
1
0
0
0
8=ROM Failure
1
0
0
1
9=Calculation Failure
The actual Frequency is greater than 32,767 Hz. or 3,276.7 Hz. (overrange).
The scaled Frequency is greater than 32,767 Hz. or 3,276.7 Hz. (overrange).
The %Full Scale calculation (based on Maximum Frequency) is greater than 32,767%.
1010-1111
10-15=Not Used
Module-defined Data Type: AB:1794_IJ2I:I:0
Member Name
Type
Default Display Style
Description
Fault
DINT
Binary
Used for Input Data Validation - 0 means the data is valid. If the connection to the module has been lost, or if the module has a severe hardware fault, 1s are represented in this input data type.
Ch0Frequency
DINT
Binary
Calculated value of Frequency for Channel 0. Frequency can be reported down to 1 or 1.0 Hz, depending on the Frequency Range setting. Below a 1 Hz value, 0 is reported. Below a 1.0 Hz value, 0.0 is reported. Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier. If input pulses are not present within the time periods allotted by these parameters, zero frequency (0 or 0.0) is reported, depending additionally on the setting of the Wire Off Fault Detection Mode. When the Frequency exceeds the module’s Max Input Frequency, the Frequency value 32,767 is reported, or- the Frequency value 3,276.7 is reported, depending on the Frequency Range data type.
When the Scaled Frequency exceeds 32,767 or 3,276.7, the Frequency value 32,767 is reported.
If a Wire Off Alarm is detected and enabled, the Frequency reported may be an Unchanged, Maximum (32,767 or 3,276.7 default or the Maximum Frequency value), or Minimum value (1 or 1.0), depending on the selection of the Wire Off Fault Alarm and the Frequency Range data type.
Range: 0...32,767 or 0.0...3,276.7 depending on state of Frequency Range data type, or Freq Range = 0 when the Frequency in Hz. is 0 - 32,767 and
Freq Range = 1 when the Frequency in Hz. is (0.0 - 3,276.7).
Ch0Acceleration
DINT
Binary
Percent of Full Scale or Acceleration for Channel 0. Value of the calculated Frequency scaled by the Maximum Frequency or, calculated value of Acceleration in Hz/s, depending on Frequency or Acceleration Alarm select data type.
Note that percent full scale is calculated accurately up to a maximum of 3,276.7%.  Beyond this maximum, the value of 3,276.7% is returned, and a Calculation Failure (9) is set in Diagnostic Status.
Frequency or Acceleration Alarm select data type = 0
Range: 0.0...3,276.7%
Frequency or Acceleration Alarm select data type = 1
Range: -32,768...32,767 Hz/sec (2’s Complement if Negative)
Ch1Frequency
DINT
Binary
Calculated value of Frequency for Channel 1. Frequency can be reported down to 1 or 1.0 Hz, depending on the Frequency Range setting. Below a 1 Hz value, 0 is reported. Below a 1.0 Hz value, 0.0 is reported. Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier. If input pulses are not present within the time periods allotted by these parameters, zero frequency (0 or 0.0) is reported depending additionally on the setting of the Wire Off Fault Detection Mode. When the Frequency exceeds the module’s Max Input Frequency, the Frequency value 32,767 is reported, or- the Frequency value 3,276.7 is reported, depending on the Frequency Range data type.
When the Scaled Frequency exceeds 32,767 or 3,276.7, the Frequency value 32,767 is reported.
If a Wire Off Alarm is detected and enabled, the Frequency reported may be an Unchanged, Maximum (32,767 or 3,276.7 default or the Maximum Frequency value), or Minimum value (1 or 1.0), depending on the selection of the Wire Off Fault Alarm and the Frequency Range data type, or Ch1Frequency Range = 0 when the Frequency in Hz. is 0 - 32,767 and Ch1Frequency Range = 1 when the Frequency in Hz. is 0.0 - 3,276.7.
Ch1Acceleration
DINT
Binary
Percent of Full Scale or Acceleration for Channel 1. Value of the calculated Frequency scaled by the Maximum Frequency or, calculated value of Acceleration in Hz/s, depending on Frequency or Acceleration Alarm select data type.
Note that the percent full scale is calculated accurately up to a maximum of 3,276.7%. Beyond this maximum, the value of 3,276.7% is returned, and a Calculation Failure (9) is set in Diagnostic Status.
Ch1Acceleration = 0
Range: 0.0...3,276.7%
Ch1Acceleration = 1
Range: -32,768...32,767 Hz/sec (2’s Complement if Negative)
Alarms
INT
Binary
Alarm data.
Ch1MissingPulse
BIT
Binary
Alarms:0; Missing Pulse Alarm (channel 1) – Indicates when no Frequency input pulse has occurred within the period determined by the Minimum Frequency Sampling Time and the Missing Pulse Multiplier. Primary control is given to the Missing Pulse Multiplier to determine when this data type is set. However, if the Missing Pulse Multiplier is set to 0, then the Minimum Frequency Sampling Time characteristics determine when this data type is set.
Ch1WireOff
BIT
Binary
Alarms:1; Wire Off Fault Alarm (channel 1) – when set, indicates when 24V dc Input (IEC 1+ or Switch Contact with shunt) Wire Off Detection has gone true for any of the Frequency or Gate inputs on a channel that has the Wire Off Fault
Select = 1
Ch1FrequencyAccel
BIT
Binary
Alarms:2; Frequency or Acceleration Alarm (channel 1) – Changes state from 0 to 1 if the calculated Frequency (actual or scaled) exceeds the user programmed Maximum Frequency, or the absolute value of calculated Acceleration/Deceleration exceeds the user programmed Maximum Acceleration Value.
The Frequency Alarm turns off when the Frequency drops below 95% of the Alarm Value.
The Acceleration Alarm turns off when the Acceleration drops below 90% of the Alarm Value.
Ch1GateState
BIT
Binary
Alarms:3; Gate Input State (channel 1) – Indicates if there is a valid signal on the gate input. This parameter is only determined once every 0.5 – 2s.
Ch1Direction4
Ch1Direction5
BIT
Binary
Alarms:4, Alarms:5; Direction (channel 1) – Indicates the current Direction of Rotation, using both the Frequency and Gate inputs. (Frequency leads Gate = Clockwise, Gate leads Frequency = CounterClockwise). Used for slow speed detection from 1 – 1,500Hz. No or Stopped rotation can be determined by the state of the Missing Pulse Alarm, when it is switched on. A missing Frequency Input generates a Missing Pulse Alarm, a missing Gate Input only generates a No Sensor Present / Detected status (3).
Ch1DiagnosticStatus_6
BIT
Binary
Alarms:6
Ch1DiagnosticStatus_7
BIT
Binary
Alarms:7
Ch0MissingPulse
BIT
Binary
Alarms:8; Missing Pulse Alarm (channel 0) – Indicates when no Frequency input pulse has occurred within the period determined by the Minimum Frequency Sampling Time and the Missing Pulse Multiplier. Primary control is given to the Missing Pulse Multiplier to determine when this data type is set. However, if the Missing Pulse Multiplier is set to 0, then the Minimum Frequency Sampling Time characteristics determine when this data type is set.
Ch0WireOff
BIT
Binary
Alarms:9; Wire Off Fault Alarm (channel 0) – When set, indicates when 24V dc Input (IEC 1+ or Switch Contact with shunt) Wire Off Detection has gone true for any of the Frequency or Gate inputs on a channel that has the Wire Off Fault
Select = 1
Ch0FrequencyAccel
BIT
Binary
Alarms:10; Frequency or Acceleration Alarm (channel 0) – Changes state from 0 to 1 if the calculated Frequency (actual or scaled) exceeds the user programmed Maximum Frequency, or the absolute value of calculated Acceleration/Deceleration exceeds the user programmed Maximum Acceleration Value.
The Frequency Alarm turns off when the Frequency drops below 95% of the Alarm Value.
The Acceleration Alarm turns off when the Acceleration drops below 90% of the Alarm Value.
Ch0GateState
BIT
Binary
Alarms:11; Gate Input State (channel 0) – Indicates if there is a valid signal on the gate input. This parameter is only determined once every 0.5 – 2s.
Ch0Direction12
Ch0Direction13
BIT
Binary
Alarms:12, Alarms:13; Direction (channel 0) – Indicates the current Direction of Rotation, using both the Frequency and Gate Inputs. (Frequency leads Gate = Clockwise, Gate leads Frequency = Counter/Clockwise). Used for slow speed detection from 1 to 1,5000 Hz. No or Stopped rotation is determined by the state of the Missing Pulse Alarm, when it is switched on. A missing Frequency Input generates a Missing Pulse Alarm. A missing Gate Input generates a No Sensor Present/Detected status (3) only.
DiagnosticStatus_14
DiagnosticStatus_15
BOOL
Decimal
Indicate the response from the module, a normal or non-normal operating condition. Follow the table below for settings.
DiagnosticStatus14
DiagnosticStatus15
Value
0
0
0=Normal Operation (No Failure)
0
1
1=Calibration Failure
1
0
2=Configuration Failure
A minimum Frequency Sample Time value other than 0-9 was selected.
1
1
3=Message Failure
0
0
4=Lead Break Detection Hardware Failure
0
1
5=Major Hardware Failure
1
0
6=EEPROM Failure
1
1
7=RAM Failure
0
0
8=ROM Failure
0
1
9=Calculation Failure
The actual Frequency is greater than 32,767 Hz. or 3,276.7 Hz. (overrange).
The scaled Frequency is greater than 32,767 Hz. or 3,276.7 Hz. (overrange).
The %Full Scale calculation (based on Maximum Frequency) is greater than 32,767%.
1010-1111
10-15=Not Used
Module-defined Data Type: AB:1794_IJ2:C:0 or AB:1797_IJ2:C:0
NOTE:
In order to enable Alarm outputs, the CommFault member in this data type must be set to 1. If this member is set to 0, the module does not return Alarm outputs. You can enable this member through the Data Monitor in the
Logix Designer
application.
Member Name
Type
Default Display Style
Description
Config1
INT
Binary
Configuration data.
Ch1MissingPulseMult0
Ch1MissingPulseMult1
BOOL
Decimal
Missing pulse multiplier (channel 1) – Used to modify the Minimum Frequency Sampling Time to allow the frequency bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more quickly.
Default = no multiplier; alarm generated immediately
Follow the table below for settings.
Ch1MissingPulseMult1
Ch1MissingPulseMult0
Missing Pulse
Multiplier
0
0
No multiplier; alarm generated immediately (normal mode with 2s delay).
0
1
X2
1
0
X8
1
1
X32
Ch1PulsesToTermSample2
Ch1PulsesToTermSample3
Ch1PulsesToTermSample4
BOOL
Decimal
Pulses to Terminate Sampling (channel 1) – Lets you calculate Frequency when a specified number of input pulses have occurred. This allows earlier reporting of the frequency than the Minimum Frequency Sampling Time, when many input pulses are occurring. Accurate frequency determination is possible without waiting for the full Minimum Frequency Sampling Time to expire.
Default = minimum frequency sampling time.
Follow the table below for settings.
Ch1PulsesToTermSample4
Ch1PulsesToTermSample3
Ch1PulsesToTermSample2
Number of pulses to terminate
sampling
0
0
0
Use minimum frequency sampling time
0
0
1
2
0
1
0
4
0
1
1
8
1
0
0
16
1
0
1
32
1
1
0
64
1
1
1
128
Ch1FrequencyRange
BOOL
Decimal
Frequency range (channel 1) – Specifies the Frequency Range of the Frequency input.
0 = 1-32767 (below 1Hz reports 0);
1 = 1.0-3276.7 (below 1.0Hz reports 0.0).
Default = 0
FaultMode
BOOL
Decimal
Fault Mode - determines how the module safe state data is used to control alarm outputs for communication and internal module faults (local fault = Wire Off Fault or Missing Pulse Alarm).
0 = safe states activated by communication only;
1 = safe states activated by any failure (communication, internal module faults, etc.)
Default = 0, safe states activated by communication only
AltPulsesToTermSamp
BOOL
Decimal
Alternate Pulses To Terminate Sampling
– Tip:
This member is used in the 1797-IJ2 only.
This member determines that you wish to use an alternate set of values to choose from, rather than the default set of values provided for Pulses To Terminate Sampling.  The Pulses To Terminate Sampling selection allows you to calculate frequency as soon as the specified number of input pulses has occurred, rather than waiting for the full Minimum Frequency Sample Time to expire.  Use of the Alternate Pulses To Terminate Sampling selection gives you another set of values to choose from when making your Pulses To Terminate Sampling selection.
Tip:
The Alternate Pulses To Terminate Sampling selection pertains to both channels.
0 = not used (default)
1 = Alternate Pulses to Terminate Sampling is selected
Ch0MissingPulseMult8
Ch0MissingPulseMult9
BOOL
Decimal
Missing pulse multiplier (channel 0) – used to modify the Minimum Frequency Sampling Time to allow the frequency bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more quickly.
Default = no multiplier; alarm generated immediately
Follow the table below for settings.
Ch0MissingPulseMult9
Ch0MissingPulseMult8
Minimum frequency
sampling
time
0
0
No multiplier; alarm generated immediately (normal mode with 2s delay).
0
1
X2
1
0
X8
1
1
X32
Ch0PulsesToTermSample10
Ch0PulsesToTermSample11
Ch0PulsesToTermSample12
BOOL
Decimal
Pulses to Terminate Sampling (channel 0) – Lets you calculate Frequency when a specified number of input pulses have occurred. This allows earlier reporting of the frequency than the Minimum Frequency Sampling Time, when many input pulses are occurring. Accurate frequency determination is possible without waiting for the full Minimum Frequency Sampling Time to expire.
Default = minimum frequency sampling time.
Follow the table below for settings.
Ch0PulsesToTermSample12
Ch0PulsesToTermSample11
Ch0PulsesToTermSample10
Number of pulses to terminate
sampling
0
0
0
Use minimum frequency sampling time
0
0
1
2
0
1
0
4
0
1
1
8
1
0
0
16
1
0
1
32
1
1
0
64
1
1
1
128
Ch0FrequencyRange
BOOL
Decimal
Frequency range (channel 0) – Specifies the Frequency Range of the Frequency input.
0 = 1-32767 (below 1Hz reports 0);
1 = 1.0-3276.7 (below 1.0Hz reports 0.0).
Default = 0
CommFaultBehavior
BOOL
Decimal
Safe state mode selection – Determines how module alarm outputs react to communication and internal module faults (local fault = Wire Off Fault or Missing Pulse Alarm).
0 = Reset outputs
1 = Hold last state
Default = 0 (reset outputs).
CommFault
BOOL
Decimal
Communication fault – Signals the module that communications has been interrupted on the network. The adapter signals that the module should execute its fault routine or go to the Safe State and control any Alarm Outputs accordingly. During normal startup, this data type must be set to 1 in the Data Monitor of the RSLogix software in order to enable operation of Alarm Outputs. When the adapter communication link is broken, the adapter will reset this to 0.  In this condition, the module must be reconfigured setting the CommFault member to 1 in order for CommFault to take effect.
Default = 0.
Ch0Frequency_Acceleration
INT
Decimal
Maximum frequency or absolute value acceleration/deceleration (channel 0) – Specifies the highest Frequency or absolute Acceleration/Deceleration value allowed on the Frequency input. 0-32,767, 0.0-3,276.7Hz. –OR– 0-32,767Hz/s depending on the Frequency Range and Frequency/Acceleration Alarm Select settings.
Ch0FrequencyMultiplier
SINT
Decimal
Frequency multiplier (channel 0) – Specifies a multiplier to scale the incoming Frequency value. 0-255.
Default = 0 – no scaling multiplication performed (x1)
Ch0FrequencyDivisor
SINT
Decimal
Frequency divisor (channel 0) – Specifies divisor to scale the incoming Frequency value. 0-255.
Default = 0 – no scaling division performed (divided by 1)
Config2
INT
Binary
Configuration data.
Ch0MissingPulse_WireOff0
Ch0MissingPulse_WireOff1
BOOL
Decimal
Wire-Off/Missing Pulse Mode (channel 0) – Sets the mode for 24V dc IEC 1+ Wire Off Input Detection and Missing Pulse Detection result for any input (Frequency or Gate). The Maximum Frequency is determined by Frequency Range and the Maximum Frequency value, and the Minimum Frequency is determined by the Frequency Range setting. The Wire Off detect time (in mode 1, 2, & 3) is 2 seconds maximum.  Follow the table below for settings.
Ch0
MissingPulse_WireOff
1
Ch0
MissingPulse_WireOff0
Channel wire-off/missing pulse fault mode
0
0
Disabled
0
1
Alarm only (frequency unchanged)
1
0
Alarm and force frequency to maximum frequency value (32767 or 3276.7 or maximum frequency value, 0).
1
1
Alarm and force frequency to minimum frequency value (0 or 0.0).
Ch0MissingPulseDelayMult2
Ch0MissingPulseDelayMult3
BOOL
Decimal
Missing Pulse Delay Multiplier (channel 0) – Specifies the number of Missing Pulse Alarms periods (Minimum Frequency Sampling Times) that are tolerated before the alarm is actually generated, if enabled. (Used to defeat the Missing Pulse Alarm during a system startup.)
Default = 0 - No multiplier; alarm generated immediately (normal mode with 2s extension delay)
Follow the table below for settings.
Ch0MissingPulseDelayMult3
Ch0MissingPulseDelayMult2
Alarm periods before alarm
generated
0
0
No multiplier; alarm generated immediately (normal mode with 2s extension delay).
0
1
2 sample periods + 2s delay before alarm.
1
0
8 sample periods + 2s delay before alarm.
1
1
32 sample periods + 2s delay before alarm.
Ch0FreqAccelSelect
BOOL
Decimal
Frequency/Acceleration (channel 0) – Determines if the value in the Maximum Frequency or Acceleration data type is a Frequency (actual or scaled) or Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
0 = frequency alarm
1 = acceleration alarm
Default = 0 - frequency alarm
Ch0AccelCalcTime5
Ch0AccelCalcTime6
BOOL
Decimal
Acceleration Calculation Time (channel 0) – Specifies the number of Frequency Sample Times over which the module calculates acceleration.
Default = 0 - Rolling Average (previous 4 samples)
Follow the table below for settings.
Ch0AccelCalcTime6
Ch0AccelCalcTime5
Acceleration Calculation Time in Frequency Sample Times
0
0
Rolling Average (previous 4 samples)
0
1
8
1
0
16
1
1
32
Ch0InitiateStartup
BOOL
Decimal
Startup Mode (channel 0) – Alerts a channel that if process start up is in progress to defeat the missing pulse alarm for a time determined by the missing pulse delay multiplier.
0 = Normal Run Mode
1 = Startup Mode - defeat/delay Missing Pulse Alarm
Default = 0 -Normal Run Mode
Ch0SamplingTime8
Ch0SamplingTime9
Ch0SamplingTime10
Ch0SamplingTime11
BOOL
Decimal
Minimum Frequency Sampling Time (channel 0) – Specifies the minimum time (in ms) the module will spend collecting pulses to determine the Frequency.
Follow the table below for settings.
Ch0SamplingTime11
Ch0SamplingTime10
Ch0SamplingTime9
Ch0SamplingTime8
Minimum Frequency
Sampling
Time – in ms
0
0
0
0
2
0
0
0
1
4
0
0
1
0
5
0
0
1
1
10
0
1
0
0
20
0
1
0
1
50
0
1
1
0
100
0
1
1
1
200
1
0
0
0
500
1
0
0
1
1000
1010 to 1111 not used – 2ms default sample time used
Ch0FrequencyInvert
BOOL
Decimal
Invert Input-Frequency (channel 0) – Selects whether to invert the Frequency input signal, if not using an Active High (24V = On) 24 Vdc IEC 1+ sensor or “Normally Open” relay or switch contact on the 24 Vdc Frequency Input terminal. Allows compatibility with an Active Low (0V = On) 24 Vdc IEC 1+ sensor or “Normally Closed” relay contact the 24 Vdc Frequency Input terminal.
0 = Normal (Active High, 24V = On)
1 = Invert input (Active Low, 0V = On)
Default = 0 - Normal (Active High, 24V = On)
Ch0GateInvert
BOOL
Decimal
Invert Input-Gate (channel 0) – Selects whether to invert the Gate input signal, if not using an Active High (24V = On) 24 Vdc IEC 1+ sensor or “Normally Open” relay or switch contact on the 24 Vdc Gate Input terminal. Allows compatibility with an Active Low (0V = On) 24 Vdc IEC 1+ sensor or “Normally Closed” relay contact on the 24 Vdc Gate Input terminal.
0 = Normal (Active High, 24V = On)
1 = Invert input (Active Low, 0V = On)
Default = 0 - Normal (Active High, 24V = On)
Ch0FrequencyFault
BOOL
Decimal
Detect Frequency Input Wire-Off (channel 0) – Selects whether to turn On or Off the 24 Vdc Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection.
Tip:
Customer devices must draw more than 0.4 mA in the On and Off State. To use this feature with relays or switches, connect a “shunt resistor” (~ 50K) across the contacts.
0 = Disable
1 = Enable
Default: = 0 - Disable
Ch0GateFault
BOOL
Decimal
Detect Gate Input Wire-Off (channel 0) – Selects whether to turn On or Off the 24 Vdc Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection.
Tip:
Customer devices must draw more than.4 mA in the On and Off State. To use this feature with relays or switches, connect a “shunt resistor” (~ 50K) across the contacts.
0 = Disabled (default)
1 = Enabled
Ch1Frequency_Acceleration
INT
Decimal
Maximum Frequency/Acceleration (channel 1) – Specifies the highest Frequency or absolute Acceleration/Deceleration value allowed on the Frequency input. 0-32,767, 0.0-3,276.7Hz. –OR–0-32,767Hz/s depending on the Frequency Range and Frequency/Acceleration Alarm Select settings.
Ch1FrequencyMultiplier
SINT
Decimal
Frequency Multiplier (channel 1) – Specifies a multiplier to scale the incoming Frequency value. 0-255.
Default = 0 – no scaling multiplication performed (x1)
Ch1FrequencyDivisor
SINT
Decimal
Frequency Divisor (channel 1) – Specifies divisor to scale the incoming Frequency value. 0-255.
Default = 0 – no scaling division performed (divided by 1)
Config3
INT
Binary
Configuration data.
Ch1MissingPulse_WireOff0
Ch1MissingPulse_WireOff1
BOOL
Decimal
Wire-Off/Missing Pulse Fault Select Mode (channel 1) – Sets the mode for 24 Vdc IEC 1+ Wire Off Input Detection and Missing Pulse Detection result for any input (Frequency or Gate). The Maximum Frequency is determined by Frequency Range and the Maximum Frequency value, and the Minimum Frequency is determined by the Frequency Range setting. The Wire Off detect time (in mode 1, 2, & 3) is 2 seconds maximum.
Follow the table below for settings.
Ch1MissingPulse_WireOff1
Ch1MissingPulse_WireOff0
Channel wire-off/missing pulse fault mode
0
0
Disabled
0
1
Alarm only (frequency unchanged)
1
0
Alarm and force frequency to maximum frequency value (32767 or 3276.7 or maximum frequency value not equal to 0).
1
1
Alarm and force frequency to minimum frequency value (0 or 0.0).
Ch1MissingPulseDelayMult2
Ch1MissingPulseDelayMult3
BOOL
Decimal
Missing pulse delay multiplier (channel 1) – Specifies the number of Missing Pulse Alarms periods (Minimum Frequency Sampling Times) which will be tolerated before the alarm is actually generated, if enabled. (Used to defeat the Missing Pulse Alarm during a system startup.)
Default = 0 – No multiplier; alarm generated immediately (normal mode with 2s extension delay)
Follow the table below for settings.
Ch1MissingPulseDelayMult3
Ch1MissingPulseDelayMult2
Alarm periods before alarm
generated
0
0
No multiplier; alarm generated immediately (normal mode with 2s extension delay).
0
1
2 sample periods + 2s delay before alarm.
1
0
8 sample periods + 2s delay before alarm.
1
1
32 sample periods + 2s delay before alarm.
Ch1FreqAccelSelect
BOOL
Decimal
Frequency or Acceleration (channel 1) – Determines if the value in the Maximum Frequency or Acceleration write data type is a Frequency (actual or scaled) or Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
0 = frequency alarm
1 = acceleration alarm
Default = 0 – frequency alarm
Ch1AccelCalcTime5
Ch1AccelCalcTime6
BOOL
Decimal
Acceleration Calculation Time (channel 1) – Specifies the number of Frequency Sample Times over which the module calculates acceleration.
Default = 0 – Rolling Average (previous 4 samples)+
Follow the table below for settings.
Ch1AccelCalcTime6
Ch1AccelCalcTime5
Acceleration Calculation Time in Frequency Sample Times
0
0
Rolling Average (previous 4 samples)
0
1
8
1
0
16
1
1
32
Ch1InitiateStartup
BOOL
Decimal
Startup Mode-(Initiate Startup Select for channel 1) – Alerts a channel that if process start up is in progress to defeat the missing pulse alarm for a time determined by the missing pulse delay multiplier.
0 = Normal Run Mode;
1 = Startup Mode – defeat/delay Missing Pulse Alarm
Default = 0 – Normal Run Mode
Ch1SamplingTime8
Ch1SamplingTime9
Ch1SamplingTime10
Ch1SamplingTime11
BOOL
Decimal
Minimum Frequency Sampling Time (channel 1) – Specifies the minimum time (in ms) the module will spend collecting pulses to determine the Frequency.
Follow the table below for settings.
Ch1SamplingTime11
Ch1SamplingTime10
Ch1SamplingTime9
Ch1SamplingTime8
Minimum Frequency Sampling
Time – in ms
0
0
0
0
2
0
0
0
1
4
0
0
1
0
5
0
0
1
1
10
0
1
0
0
20
0
1
0
1
50
0
1
1
0
100
0
1
1
1
200
1
0
0
0
500
1
0
0
1
1000
1010 to 1111 not used – 2ms default sample time used
Ch1FrequencyInvert
BOOL
Decimal
Invert Frequency (channel 1) – Selects whether to invert the Frequency input signal, if not using an Active High (24V = On) 24 Vdc IEC 1+ sensor or “Normally Open” relay or switch contact on the 24 Vdc Frequency Input terminal. Allows compatibility with an Active Low (0V = On) 24 Vdc IEC 1+ sensor or “Normally Closed” relay contact on the 24 Vdc Frequency Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On).
Default = 0 – Normal (Active High, 24V = On)
Ch1GateInvert
BOOL
Decimal
Invert -Gate (channel 1)
Selects whether to invert the Gate input signal, if not using an Active High (24V = On) 24 Vdc IEC 1+ sensor or “Normally Open” relay or switch contact on the 24 Vdc Gate Input terminal. Allows compatibility with an Active Low (0V = On) 24 Vdc IEC 1+ sensor or “Normally Closed” relay contact on the 24 Vdc Gate Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On)
Default = 0 – Normal (Active High, 24V = On)
Ch1FrequencyFault
BOOL
Decimal
Detect Frequency Fault (channel 1)
Selects whether to turn On or Off the 24 Vdc Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection.
Tip:
Customer devices must draw more than 0.4 mA in the On and Off State. To use this feature with relays or switches, connect a “shunt resistor” (~ 50K) across the contacts.
0 = Disable,
1 = Enable
Default: = 0 – Disable
Ch1GateFault
BOOL
Decimal
Detect Gate (channel 1)
Selects whether to turn On or Off the 24 Vdc Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection.
Tip:
Customer devices must draw more than.4 mA in the On and Off State. To use this feature with relays or switches, connect a “shunt resistor” (~ 50K) across the contacts.
0 = Disable,
1 = Enable
Default = 0 – Disable
Module-defined Data Type: AB:1794_IJ2I:C:0
NOTE:
In order to enable Alarm outputs, the CommFault member in this data type must be set to 1. If this member is set to 0, the module does not return Alarm outputs. You can enable this member through the Data Monitor in the
Logix Designer
application.
Member Name
Type
Default Display Style
Description
Config1
INT
Binary
Configuration data.
Ch1MissingPulseMult_0
BIT
Binary
Missing pulse multiplier (channel 0) – Used to modify the Minimum Frequency Sampling Time to allow the frequency bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more quickly.
Default = no multiplier; alarm generated immediately
Follow the table below for settings.
Ch1MissingPulseMult_1
BIT
Binary
Missing pulse multiplier (channel 1) – Used to modify the Minimum Frequency Sampling Time to allow the frequency bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more quickly.
Default = no multiplier; alarm generated immediately
Follow the table below for settings.
Ch1FreqAccelSelect
BIT
Binary
Frequency/Acceleration (channel 1) – Determines if the value in the Maximum Frequency or Acceleration data type is a Frequency (actual or scaled) or Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
0 = frequency alarm
1 = acceleration alarm
Default = 0 - frequency alarm
Reserved
BIT (3-7)
Ch0MissingPulseMult_8
BIT
Binary
Missing pulse multiplier (channel 0) – Used to modify the Minimum Frequency Sampling Time to allow the frequency bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more quickly.
Default = no multiplier; alarm generated immediately
Follow the table below for settings.
Ch0MissingPulseMult_9
BIT
Binary
Missing pulse multiplier (channel 0) – Used to modify the Minimum Frequency Sampling Time to allow the frequency bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more quickly.
Default = no multiplier; alarm generated immediately
Follow the table below for settings.
Ch0MissingPulseMult1
Ch0MissingPulseMult0
Missing Pulse
Multiplier
0
0
No multiplier; alarm generated immediately (normal mode with 2s delay).
0
1
X2
1
0
X8
1
1
X32
Ch0FreqAccelSelect
BIT
Binary
Frequency/Acceleration (channel 0) – Determines if the value in the Maximum Frequency or Acceleration data type is a Frequency (actual or scaled) or Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
0 = frequency alarm
1 = acceleration alarm
Default = 0 - frequency alarm
Reserved
BIT (11-15)
Ch0PulsesToTermSample
Ch1PulsesToTermSample
SINT
Pulses to Terminate Sampling (channel 1) – Lets you calculate Frequency when a specified number of input pulses have occurred. This allows earlier reporting of the frequency than the Minimum Frequency Sampling Time, when many input pulses are occurring. Accurate frequency determination is possible without waiting for the full Minimum Frequency Sampling Time to expire.
Default = minimum frequency sampling time.
Follow the table below for settings.
Ch1PulsesToTermSample12
Ch1PulsesToTermSample11
Ch1PulsesToTermSample10
Number of pulses to terminate
sampling
0
0
0
Use minimum frequency sampling time
0
0
1
2
0
1
0
4
0
1
1
8
1
0
0
16
1
0
1
32
1
1
0
64
1
1
1
128
Ch0FrequencyMultiplier
SINT
Frequency multiplier (channel 0) – Specifies a multiplier to scale the incoming Frequency value. 0-255.
Default = 0 – no scaling multiplication performed (x1)
Ch0FrequencyDivisor
SINT
Frequency divisor (channel 0) – Specifies divisor to scale the incoming Frequency value. 0-255.
Default = 0 – no scaling division performed (divided by 1)
Config2
INT
Binary
Configuration data
Ch0MissingPulse_WireOff_0
Ch0MissingPulse_WireOff_1
BIT
Binary
Wire-Off/Missing Pulse Mode (channel 0) – Sets the mode for 24V dc IEC 1+ Wire Off Input Detection and Missing Pulse Detection result for any input (Frequency or Gate). The Maximum Frequency is determined by Frequency Range and the Maximum Frequency value, and the Minimum Frequency is determined by the Frequency Range setting. The Wire Off detect time (in mode 1, 2, & 3) is 2 seconds maximum. Follow the table below for settings.
Ch0
MissingPulse_WireOff
1
Ch0
MissingPulse_WireOff0
Channel wire-off/missing pulse fault mode
0
0
Disabled
0
1
Alarm only (frequency unchanged)
1
0
Alarm and force frequency to maximum frequency value (32767 or 3276.7 or maximum frequency value, 0).
1
1
Alarm and force frequency to minimum frequency value (0 or 0.0).
Ch0MissingPulseDelayMult_2
Ch0MissingPulseDelayMult_3
BIT
Binary
Missing Pulse Delay Multiplier (channel 0) – Specifies the number of Missing Pulse Alarms periods (Minimum Frequency Sampling Times) that are tolerated before the alarm is actually generated, if enabled. (Used to defeat the Missing Pulse Alarm during a system startup.)
Default = 0 - No multiplier; alarm generated immediately (normal mode with 2s extension delay)
Follow the table below for settings.
Ch0
MissingPulse_WireOff
1
Ch0
MissingPulse_WireOff0
Channel wire-off/missing pulse fault mode
0
0
Disabled
0
1
Alarm only (frequency unchanged)
1
0
Alarm and force frequency to maximum frequency value (32767 or 3276.7 or maximum frequency value, 0).
1
1
Alarm and force frequency to minimum frequency value (0 or 0.0).
Reserved
BIT (4)
Ch0AccelCalcTime_5
Ch0AccelCalcTime_6
BIT
Binary
Acceleration Calculation Time (channel 0) – Specifies the number of Frequency Sample Times over which the module calculates acceleration.
Default = 0 - Rolling Average (previous 4 samples)
Follow the table below for settings.
Ch0AccelCalcTime6
Ch0AccelCalcTime5
Acceleration Calculation Time in Frequency Sample Times
0
0
Rolling Average (previous 4 samples)
0
1
8
1
0
16
1
1
32
Ch0InitiateStartup
BIT
Binary
Startup Mode (channel 0) – Alerts a channel that if process start up is in progress to defeat the missing pulse alarm for a time determined by the missing pulse delay multiplier.
0 = Normal Run Mode
1 = Startup Mode - defeat/delay Missing Pulse Alarm
Default = 0 -Normal Run Mode
Ch0SamplingTime_8
Ch0SamplingTime_9
Ch0SamplingTime_10
Ch0SamplingTime_11
BIT
Binary
Minimum Frequency Sampling Time (channel 0) – Specifies the minimum time (in ms) the module spends collecting pulses to determine the Frequency.
Follow the table below for settings.
Ch0SamplingTime11
Ch0SamplingTime10
Ch0SamplingTime9
Ch0SamplingTime8
Minimum Frequency
Sampling
Time – in ms
0
0
0
0
2
0
0
0
1
4
0
0
1
0
5
0
0
1
1
10
0
1
0
0
20
0
1
0
1
50
0
1
1
0
100
0
1
1
1
200
1
0
0
0
500
1
0
0
1
1000
1010 to 1111 not used – 2 ms default sample time used
Ch0FrequencyInvert
BIT
Binary
Invert Input-Frequency (channel 0) – Selects whether to invert the Frequency input signal, if not using an Active High (24V = On) 24V dc IEC 1+ sensor or Normally Open relay or switch contact on the 24V dc Frequency Input terminal. Allows compatibility with an Active Low (0V = On) 24V dc IEC 1+ sensor or Normally Closed relay contact the 24V dc Frequency Input terminal.
0 = Normal (Active High, 24V = On)
1 = Invert input (Active Low, 0V = On)
Default = 0 - Normal (Active High, 24V = On)
Ch0GateInvert
BIT
Binary
Invert Input-Gate (channel 0) – Selects whether to invert the Gate input signal, if not using an Active High (24V = On) 24V dc IEC 1+ sensor or Normally Open relay or switch contact on the 24V dc Gate Input terminal. Allows compatibility with an Active Low (0V = On) 24V dc IEC 1+ sensor or Normally Closed relay contact on the 24V dc Gate Input terminal.
0 = Normal (Active High, 24V = On)
1 = Invert input (Active Low, 0V = On)
Default = 0 - Normal (Active High, 24V = On)
Ch0FrequencyFault
BIT
Binary
Detect Frequency Input Wire-Off (channel 0) – Selects whether to turn On or Off the 24V dc Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection. Note that Customer devices must draw more than 0.4 mA in the On and Off State. To use this feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
0 = Disable
1 = Enable
Default: = 0 - Disable
Ch0GateFault
BIT
Binary
Detect Gate Input Wire-Off (channel 0) – Selects whether to turn On or Off the 24V dc Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection. Note that Customer devices must draw more than.4 mA in the On and Off State. To use this feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
0 = Disabled (default)
1 = Enabled
Ch1FrequencyMultiplier
SINT
Frequency Multiplier (channel 1) – Specifies a multiplier to scale the incoming Frequency value. 0-255.
Default = 0 – no scaling multiplication performed (x1)
Ch1FrequencyDivisor
SINT
Frequency Divisor (channel 1) – Specifies divisor to scale the incoming Frequency value. 0-255.
Default = 0 – no scaling division performed (divided by 1)
Config3
INT
Binary
Configuration data
Ch1MissingPulse_WireOff_0
Ch1MissingPulse_WireOff_1
BIT
Binary
Wire-Off/Missing Pulse Fault Select Mode (channel 1) – Sets the mode for 24V dc IEC 1+ Wire Off Input Detection and Missing Pulse Detection result for any input (Frequency or Gate). The Maximum Frequency is determined by Frequency Range and the Maximum Frequency value, and the Minimum Frequency is determined by the Frequency Range setting. The Wire Off detect time (in mode 1, 2, & 3) is 2 seconds maximum.
Follow the table below for settings.
Ch1MissingPulse_WireOff1
Ch1MissingPulse_WireOff0
Channel wire-off/missing pulse fault mode
0
0
Disabled
0
1
Alarm only (frequency unchanged)
1
0
Alarm and force frequency to maximum frequency value (32,767 or 3276.7 or maximum frequency value not equal
to 0).
1
1
Alarm and force frequency to minimum frequency value (0 or 0.0).
Ch1MissingPulseDelayMult_2
Ch1MissingPulseDelayMult_3
BIT
Binary
Missing pulse delay multiplier (channel 1) – Specifies the number of Missing Pulse Alarms periods (Minimum Frequency Sampling Times) that are tolerated before the alarm is actually generated, if enabled. (Used to defeat the Missing Pulse Alarm during a system startup.)
Default = 0 – No multiplier; alarm generated immediately (normal mode with 2s extension delay)
Follow the table below for settings.
Ch1MissingPulseDelayMult3
Ch1MissingPulseDelayMult2
Alarm periods before
alarm generated
0
0
No multiplier; alarm generated immediately (normal mode with 2s extension delay).
0
1
2 sample periods + 2s delay before alarm.
1
0
8 sample periods + 2s delay before alarm.
1
1
32 sample periods + 2s delay before alarm.
Reserved
BIT (4)
Ch1AccelCalcTime_5
Ch1AccelCalcTime_6
BIT
Binary
Acceleration Calculation Time (channel 1) – Specifies the number of Frequency Sample Times over which the module calculates acceleration.
Default = 0 – Rolling Average (previous 4 samples)+
Follow the table below for settings.
Ch1AccelCalcTime6
Ch1AccelCalcTime5
Acceleration Calculation Time in Frequency Sample Times
0
0
Rolling Average (previous 4 samples)
0
1
8
1
0
16
1
1
32
Ch1InitiateStartup
BIT
Binary
Startup Mode-(Initiate Startup Select for channel 1) – Alerts a channel that if process start up is in progress to defeat the missing pulse alarm for a time determined by the missing pulse delay multiplier.
0 = Normal Run Mode;
1 = Startup Mode – defeat/delay Missing Pulse Alarm
Default = 0 – Normal Run Mode
Ch1SamplingTime_8
Ch1SamplingTime_9
Ch1SamplingTime_10
Ch1SamplingTime_11
BIT
Binary
Minimum Frequency Sampling Time (channel 1) – Specifies the minimum time (in ms) the module spends collecting pulses to determine the Frequency.
Follow the table below for settings.
Ch1SamplingTime11
Ch1SamplingTime10
Ch1SamplingTime9
Ch1SamplingTime8
Minimum Frequency Sampling
Time – in ms
0
0
0
0
2
0
0
0
1
4
0
0
1
0
5
0
0
1
1
10
0
1
0
0
20
0
1
0
1
50
0
1
1
0
100
0
1
1
1
200
1
0
0
0
500
1
0
0
1
1000
1010 to 1111 not used – 2ms default sample time used
Ch1FrequencyInvert
BIT
Binary
Invert Frequency (channel 1) – Selects whether to invert the Frequency input signal, if not using an Active High (24V = On) 24 V dc IEC 1+ sensor or Normally Open relay or switch contact on the 24V dc Frequency Input terminal. Allows compatibility with an Active Low (0V = On) 24 Vdc IEC 1+ sensor or Normally Closed relay contact on the 24V dc Frequency Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On).
Default = 0 – Normal (Active High, 24V = On)
Ch1GateInvert
BIT
Binary
Invert -Gate (channel 1)
Selects whether to invert the Gate input signal, if not using an Active High (24V = On) 24V dc IEC 1+ sensor or Normally Open relay or switch contact on the 24V dc Gate Input terminal. Allows compatibility with an Active Low (0V = On) 24V dc IEC 1+ sensor or Normally Closed relay contact on the 24V dc Gate Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On)
Default = 0 – Normal (Active High, 24V = On)
Ch1FrequencyFault
BIT
Binary
Detect Frequency Fault (channel 1)
Selects whether to turn On or Off the 24V dc Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection. Note that customer devices must draw more than 0.4 mA in the On and Off State. To use this feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
0 = Disable,
1 = Enable
Default: = 0 – Disable
Ch1GateFault
BIT
Binary
Detect Gate (channel 1)
Selects whether to turn On or Off the 24V dc Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection. Note that customer devices must draw more than.4 mA in the On and Off State. To use this feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
0 = Disable,
1 = Enable
Default = 0 – Disable
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.